Operating Manual 

Digital Field Display PA 440 

Headquarters 

BD SENSORS GmbH 
BD-Sensors-Str. 1 
D - 95199 Thierstein 
Germany 
Tel.: +49 (0) 9235-9811-0 
Fax: +49 (0) 9235-9811-11 

Eastern Europe 

BD SENSORS s.r.o. 
Hradištská 817 
CZ - 687 08 Buchlovice 
Czech Republic 
Tel.: +42 (0) 572-4110 11 
Fax: +42 (0) 572-4114 97 

Russia  

BD SENSORS RUS 
39a, Varshavskoe shosse 
RU - Moscow 117105 
 
Russia 
Tel.: +7 (0) 95-380 1683 
Fax: +7 (0) 95-380 1681 

China  

BD SENSORS China Co, Ltd. 
Room B, 2nd Floor, Building 10, 
No. 1188 Lianhang Rd. 
201112 Shanghai,  
China 
Tel.: +86 (0) 21-51600 190 
Fax: +86 (0) 21-33600 613 

 

further agencies in: 

EUROPE

 

 

Belgium 

 

Denmark 

 

Finland 

 

France 

 

Great Britain 

 

Greece 

 

Italy 

 

Lithuania 

 

Luxemburg 

 

Netherlands 

 

Norway

 

 

  Poland 

 

 Portugal 

 

 

Romania 

 

Sweden 

 

Switzerland 

 

Slovakia 

 

Spain 

 

Turkey 

 

UK 

 

Ukraine

 

AFRICA 

 

Egypt

 

 

South Africa

 

ASIA 

 

India 

 

Iran 

 

Israel 

 

Japan 

 

Kazakhstan 

 

Malaysia 

 

Singapore 

 

Taiwan 

 

Thailand 

 

Vietnam 

AUSTRALIA

 

 

The  addresses  of  our  distribution  partners  are  listed  on  our 
homepage 

www.bdsensors.com

. It is possible to download 

data  sheets,  operating  manuals,  ordering  codes  and  certifi-
cates, as well. 

1. General information 

1.1 Information on the operating manual 

This  operating  manual  contains  important  information  on 
proper  usage  of  the  device.  Read  this  operating  manual 
carefully  before  installing  and  starting  up  the  pressure 
measuring device. 

Adhere to the safety  notes and  operating instructions which 
are  given  in  the  operating  manual.  Additionally  applicable 
regulations  regarding  occupational  safety,  accident  preven-
tion  as  well  as  national  installation  standards  and  engineer-
ing rules must be complied with! 

This  operating  manual  is  part  of  the  device,  must  be  kept 
nearest its location, always accessible to all employees. 

This  operating  manual  is  copyrighted.  The  contents  of  this 
operating  manual  reflect  the  version  available  at  the  time  of 
printing.  It  has  been  issued  to  our  best  knowledge.  BD 
SENSORS is not liable for any incorrect statements and their 
effects. 

– Technical modifications reserved – 

1.2 Symbols used 

 

DANGER!  –  dangerous  situation,  which  may  result  in 
death or serious injuries 

 

WARNING!  –  potentially  dangerous  situation,  which 
may result in death or serious injuries 

 

CAUTION! – potentially dangerous situation, which may 
result in minor injuries 

!

 

CAUTION! – potentially dangerous situation, which may 
result in physical damage  

 

NOTE  –  tips  and  information  to  ensure  a  failure-free 
operation 

1.3 Target group 

 

WARNING! To avoid operator hazards and damages of 
the device, the following instructions have to be worked 
out by qualified technical personnel. 

1.4 Limitation of liability 

By  non-observance  of  the  operating  manual,  inappropriate 
use,  modification  or  damage,  no  liability  is  assumed  and 
warranty claims will be excluded. 

1.5 Intended use 

-  The  field  display  PA  440  is  supplied  by  the  analogue 

current loop and shows the measured value on the dis-
play. For monitoring the limit values optionally up to two 
PNP open collector-contacts are available. As standard 
the  PA  440  is  equipped  with  a  LC-display,  optionally  a 
LED-display is deliverable. 

-  The configuration is menu-driven  via two  push buttons 

located in the front. Following parameters could be con-
figured:  decimal  point,  zero  point,  end  point,  switch-on 
and  switch-off  points,  etc.  Those  parameters  are  being 
stored in an EEPROM and, thus, are being kept also in 
case of power breakdown. Limit exceeding in both direc-
tions  can  be  displayed  as  a  message.  Furthermore  an 
access protection is provided. 

-  It is the operator's responsibility to check and verify the 

suitability  of  the  device  for  the  intended  application.  If 
any doubts remain, please contact our sales department 
in  order  to  ensure  proper  usage.  BD  SENSORS  is  not 
liable for any incorrect selections and their effects! 

-  The  technical  data  listed  in  the  current  data  sheet  are 

engaging and must be complied with. If the data sheet is 
not  available,  please  order  or  download  it  from  our 
homepage.  (http://www.bdsensors.com/products/down-
load/datasheets) 

 

WARNING!

 

Danger through improper usage!  

1.6 Package contents 

Please verify that all listed parts are undamaged included in 
the  delivery  and  check  for  consistency  specified  in  your 
order: 

-  field display PA 440 

-  sheet of unit labels  

-  mounting instructions 

1.7 UL – Approval 

The UL – Approval was done with respect to U.S. standards 
norms  which  also  correspond  with  the  applicable  Canadian 
standards norms for safety. 
Note the following points, so that devices fulfils the demands 
of UL approval: 

-  The transmitter shall be supplied by Limited Energy 

Source (per UL 61010) or NEC Class 2 Power Source. 

-  only indoor use  
-  maximum operating voltage: see technical data 
-  use only batteries with UL certification 

2. Product identification 

The  device  can  be  identified  by  its  manufacturing  label.  It 
provides  the  most  important  data.  By  the  ordering  code  the 
product can be clearly identified. The programme version of 
the  firmware,  (e.  g.  P06)  will  appear  for  about  1  second  in 
the display after starting up the device. Please hold it ready 
for inquiry calls. 

Fig. 1 manufacturing label 

!

 

The manufacturing label must not be removed from the 
device! 

3. Mechanical installation 

3.1 Mounting and safety instructions 

 

WARNING!

 

Install the device only when currentless! 

 

WARNING!

 

This  device  may  only  be  installed  by 

qualified  technical  personnel  who  has  read  and  under-
stood the operating manual! 

!

 

Handle 

this 

high-sensitive 

electronic 

precision 

measuring  device  with  care,  both  in  packed  and 
unpacked condition! 

!

 

There are no modifications/changes to be made on the 
device.  

!

 

Do not throw the package/device! 

!

 

Remove  packaging  only  directly  before  starting  up  the 
device to avoid any damage! 

!

 

Do  not  use  any  force  when  installing  the  device  to 
prevent damage of the device and the transmitter! 

3.2 General installation steps 

-  Carefully  remove  the  pressure  measuring  device  from 

the package and dispose of the package properly. 

-  Next  the  field  display  has  to  be  mount  stationary  on  a 

suitable  fixing  location  via  two  appropriate  fastening 
screws. 

3.3 Lead in the transmitter cable 

-  Lead in the connecting cable of the transmitter through 

the cable gland on the left side. The cable length inside 
the  terminal  box  has  to  be  long  enough  for  connecting 
the  cords  with  the  terminal  clamps  on  the  left  
(SENSOR). 

-  Then  tighten  the  cable  gland  by  hand.  Take  care  that 

the cable is strain-relieved. 

-  Pay  attention  that  the  PTFE-filter  on  the  gauge  refer-

ence  of  BD SENSORS-transmitters  may  not  be  dam-
aged or removed. 

3.4 Lead in the supply line 

-  Lead  the  supply  line  through  the  cable  gland  on  the 

right side. The cable length inside the terminal box has 
to  be  long  enough  for  connecting  the  cords  with  the 
terminal clamps on the right (SUPPLY). 

-  Then  tighten  the  cable  gland  by  hand.  Take  care  that 

the cable is strain-relieved. 

4. Electrical Installation 

 

WARNING!

 

Install the device only when currentless! 

 

The  supply  must  correspond  to  the  safety  class  II 
(protective insulation)! 

 

The  transmitter  shall  be  supplied  by  Limited  Energy 
Source (per UL 61010) or NEC Class 2 Power Source! 

Open the top cover; establish the electrical connection of 
the device according to the following table and the wiring 
diagram. Screw the top cover onto the box again. 

Pin configuration: 

 

De-

sign-
ation 

 

Terminal 

block 

Electrical 

connection 

(cable colours of 

BD SENSORS 

transmitters) 

to connected with 

GND  SENSOR 

Potential reference 

clamp  

(yellow/green ) 

cable shield of 
transmitter 

VS-  SENSOR 

Supply - (brown) 

neg. connecting 
cable of transmitter 

VS+  SENSOR

 

 (white) 

pos. connecting 
cable of transmitter 

SP2 

SP 

Contact 1 

connecting cable 
of transmitter 
for contact 1  

SP1 

SP

 

Contact 2 

connecting cable 
of transmitter 
for contact 2 

VS+  SUPPLY

 

 

pos. connecting 
cable for pressure 
signal 

VS-  SUPPLY

 

Supply -

 

neg. connecting 
cable for pressure 
signal 

GND  SUPPLY 

Potential  

reference clamp 

cable shield of 
supply line 

 

 

For  the  electrical  connection  a  shielded  and  twisted 
multicore cable is recommended. 

 

The  ground  wires  of  all  components  have  to  be  
connected when installing! 

Supply: 

The  supply  created  by  the  electronics  of  the  device  is 
approx.  6.5  V

DC

.  Please  take  this  into  consideration  when 

planning  your  power  supply.  The  tolerances  for  the  power 
supply can be calculated as follows: 

Minimum supply: 

V

S

min

 = 

V

min

TR

 + 6.5V 

 

Maximum supply: 

V

S

max

 = 

V

max

TR

 + 6.5V 

 

 

V

min TR 

= minimum supply of the used 2-wire transmitter 

 

V

maxTR

 

= maximum supply of the used 2-wire transmitter 

www.bdsensors.com 

EN 

 

input  

type  

serial  

 

designation 

number 

 

output 

ordering code 

Reviews: