33
A P P E N D I X A
A P P E N D I X A
DATA/CONFIGURATION COMMAND
DATA/CONFIGURATION COMMAND
S U M M A R Y
S U M M A R Y
The tables below summarize the data and configuration commands supported by
the V79 PDI-1 and V80 PDI-2 I/O modules:
V79 PDI-1 & V80 PDI-2 COMMAND SUMMARY
Command
Description
CB
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Clear Event Buffer. Clear all buffered event samples.
CC
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Clear Event Counter(s)
CR
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Clear Event Latch Data
RA
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report All Buffered Events
RC
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Event Counter(s)
RD
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Event Duration(s)
RL
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Event Latch Data
RO
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Event Counter and Reset
RR
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Event Latch Data
RS
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Single Buffered Event (first in, first out)
SA
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Read and report the current state of the selected input(s).
SL
c
<cr>
(
c
=Ch# 1 to 16, 0=all)
Report Latest Event
* Multiple channels are selected using 4 formats.
Examples:
SA1,2,3,4,5,6,7,8<cr>
,
SA1-8<cr>
,
SA0<cr>
,
SA1,2,4-8<cr>
V79 PDI-1 & V80 PDI-2 DYNAMIC CONFIGURATION COMMAND SUMMARY
Command
Description
DB
n
<cr>
(
n
=0-65535ms)
Debounce Delay
DF
n
<cr>
(
n
=1 or 2)
Data Format. 1=Hexadecimal and 2=Decimal.
RM
n
<cr> (
n
=1 to 3)
Reporting Method. 1=Command, 2=Immediate, and 3=Schedule.
TT
n
<cr> (
n
=1 or 2)
Time Tag. 1=Enable and 2=Disable.