17
4.5
EVENT SAMPLE PRESENTATION
Event Sample presentation varies slightly in format depending on module
configuration. Entries such as, time tag, data format, number of active channels,
etc. all change how event samples appear to a host-controller. However, all event
samples are presented in the same basic order of fields as follows:
UU:MM,CC 1
or
0
MM/DD/YY HH:MM:SS
where,
UU
is the M Series Unit Number
MM
is the PDI Module Number
CC
is the PDI Channel Number
1
channel status is "closed" (PDI-1) or has voltage applied
(PDI-2)
0
channel status is "open" (PDI-2) or has no voltage applied
(PDI-2)
MM
is the month (if Time Tag enabled)
DD
is the day (if Time Tag enabled)
YY
is the year (if Time Tag enabled)
HH
is the hour (if Time Tag enabled)
MM
is the minute (if Time Tag enabled)
SS
is the second (if Time Tag enabled)
The following example shows event samples received using immediate or schedule
reporting where the PDI is installed in Unit 1 Module 15 with Time Tagging
enabled:
1:15,1 1 11/18/93 09:12:22<cr><lf>
1:15,2 1 11/18/93 09:12:22<cr><lf>
UNIT#
MODULE#
CHANNEL#
CHANNEL STATUS
DATE
TIME
Summary of Contents for V79 PDI-1