LINYITOMAT PLUS BOILER TECHNICAL INFORMATION
•
Boiler flue gas temperature could be change between 180-300ºC Under
normal conditions. This value may be a little more at first burning. At the
minimum power, it is 130-180ºC according to room temperature.
•
For Linyitomat PLUS LP 20- 80
boiler water temperatures was
limited like shown at the table.
•
It is mandatory that the boiler return
and out water temperature have to
be limits that are given at the table.
•
If the return water temperature low
than at the table, an auxiliary pump
have to be used.
•
In case circulation pump doesn’t run, flame situation should be checked in
the boiler. Level of coal should be check if the coal level is enough for
increasing of the water temperature. In that case measure must be taken.
•
Fuel loading mouth measurements
A(mm)
B(mm)
LĐNYĐTOMAT 20 PLUS
330
203
LĐNYĐTOMAT 40 PLUS
430
210
LĐNYĐTOMAT 60 PLUS
430
220
B
LĐNYĐTOMAT 80 PLUS
530
250
A
In case of
lignite coal
usage
Min.Boiler water
inlet temperature
o
C
50
o
C
Min. Boiler water
outlet temperature
o
C
60
o
C
At 80-60ºC operating
tempearature
Operating temparature range
Shunt pump
flow capacity
Calculating method of the auxiliary pump flow capacity For LP 80
Summary of Contents for Linyitomat Plus
Page 3: ...63 9810 0293 Rev 00 08 09 2008 3 LĐNYĐTOMAT PLUS 20 40 60 80 ...
Page 4: ...63 9810 0293 Rev 00 08 09 2008 4 ...
Page 5: ...63 9810 0293 Rev 00 08 09 2008 5 Top view Front view Right side view Left side view ...
Page 29: ...63 9810 0293 Rev 00 08 09 2008 29 AUTOMATIC Electronic Control Board Manuel Automatic Control ...
Page 30: ...63 9810 0293 Rev 00 08 09 2008 30 Electricity connection circuit scheme ...
Page 31: ...63 9810 0293 Rev 00 08 09 2008 31 ...
Page 32: ...63 9810 0293 Rev 00 08 09 2008 32 Boiler installation scheme with hot water tank ...