2
TECHNICAL DATA
MODEL
TECNO 34-L
TECNO 44-L
POWER
(1)
OUTPUT
(1)
2nd stage
kW
154 - 395
235 - 485
Mcal/h
132 - 340
204 - 418
kg/h
13 - 33,6
20 - 41
1st stage
kW
97 - 154
155 - 235
Mcal/h
83 - 133
133 - 204
kg/h
8,3 - 13
13 - 20
FUEL
LIGHT OIL
- net calorific value
kWh/kg
Mcal/kg
11,8
10,2 (10.200 kcal/kg)
- density
kg/dm
3
0,82 - 0,85
- viscosity at 20 °C
mm
2
/s max
6 (1,5 °E - 6 cSt)
OPERATION
• Intermittent (min. 1 stop in 24 hours).
• Two-stage (high and low flame) and single-stage (all - nothing).
NOZZLES
number
2
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 ~ +/-10%
50/60 - single-phase
ELECTRIC MOTOR
rpm
W
V
A
2800
300
220 - 240
2,4
2800
420
230
2.65
MOTOR CAPACITOR
F/V
12.5/450
16/425
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 2 x 12 kV
0.2 A - 30 mA
PUMP
output (at 12 bar)
pressure range
fuel temperature
kg/h
bar
°C max
45
7 - 14
60
67
10 - 20
60
ELECTRICAL POWER CONSUMPTION
W max
600
700
PROTECTION LEVEL
IP40
IN CONFORMITY WITH DIRECTIVES
2014/30/UE - 2014/35/UE - 2006/42/EC
dB(A)
68
79
70
81
(1)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The
sound power is measured with the “Free Field” method, as per EN 15036, and according to an “Accuracy: Category 3” measuring accuracy,
as set out in EN ISO 3746.
VARIANTS
Model
Electrical supply
Blast tube length Lmm
TECNO 34-L
single-phase
216
TECNO 44-L
single-phase
216
ACCESSORIES
(optional)
:
• LONG HEAD KIT:
Burner
TECNO 34-L
TECNO 44-L
Code
3010426
3010425
• CLEAN CONTACT KIT
code
3010419
• KIT GROUND FAULT INTERRUPTER
code
3010448
• KIT HOURCOUNTER
code
3010450
• KIT POST-PURGING
code
3010453
• RADIO DISTURBANCEPROTECTION KIT
code
3010386
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a con-
sequence of depressurisation or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations. Degassing units are provided in two versions:
CODE
3010054
without filter
CODE
3010055
with filter
Degassing unit characteristics
•
Burner output
: 80 kg/h max
•
Light oil pressure
: 0.7 bar max
•
Ambient temperature
: 40 °C max
•
Light oil temperature
: 40 °C max
•
Attachment connectors
: 1/4 inch
NOISE LEVEL
(2)
SOUND PRESSURE
SOUND POWER
Summary of Contents for TECNO 34-L
Page 2: ......
Page 20: ......
Page 38: ......
Page 58: ...20 0 1 1 0 2 3 0 0 0 1 1 1 1 0 2 0 TECNO 44 L ...
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ...N 6119 6 1212 CE Baxi Calefacción S L U 2012 ...