1. Remove the service panel.
D
Service panel for AWHP 4.5 MR
E
Service panel for AWHP 6 MR-3, AWHP 8 MR-2,
AWHP 11 MR-2 , AWHP 16 MR-2
F
Service panel for AWHP 11 TR-2, AWHP 16 TR-2
2. This step is only valid for AWHP 4.5 MR: Remove the earth connec
tion present on the appliance and discard.
3. Check the cross-section of the cable used, as well as its protection
in the distribution board.
4. Step 4 is only valid for the AWHP 4.5 MR model. Secure the screw
and square washer provided on the stripped part of the earth wire
.
Danger
The stripped part of the earth wire must be fitted underneath the
washer against the base frame.
5. Connect the earth wire.
Danger
The earth wire must be 10 mm longer than the N and L wires.
6. Connect the cables to the appropriate terminals.
7. Feed the cable into the cable duct and adjust the length of the cable
accordingly. Lock it in position with a cable clamp or a traction ar
rester device.
Caution
Danger of electric shock: the length of the conductors between the
traction arrester device and the terminal blocks must be such that
the active conductors are put under tension before the earth con
ductor.
Fig.61
MW-1000787-3
1
2
MW-1000787-2
1
7
D
E
F
230V~
NEW
4
5
6
7
230V~
L
N
10mm
1
7
7 Installation
7685645 - v04 - 07032018
AWHP-2 iMPI
57