7.3.2
Connecting the safety valve drain pipe
1. Remove the front panel by pulling firmly upwards.
2. Pass the outlet pipe from the safety valve through the opening provi
ded for this purpose.
3. Connect the outlet pipe to the waste water discharge.
Caution
The discharge pipe in the safety valve or unit must not be blocked.
7.4
Refrigeration connections
7.4.1
Installing the refrigeration link
1. Install the refrigerant connection pipes between the indoor module
and the outdoor unit.
2. Ensure the minimum bending radii of 100 to 150 mm and the pipe
characteristics are observed.
3. Cut the pipes with a pipe cutter and deburr; angle the opening in the
pipe downwards to ensure no particles can get inside.
4. After completing the installation and all checks necessary before
commissioning, add refrigerant fluid if the refrigeration connection
pipes are more than 10 metres long.
Quantity of refrigerant fluid to be added
If the refrigeration connection pipes are more than 10 metres long, add
more refrigerant fluid.
Caution
Prevent oil traps.
If the pipes are not connected immediately, plug them to prevent
moisture from entering.
Tab.18 For AWHP 4.5 MR
Length of refrig
eration pipe
7 m
10 m
15 m
20 m
30 m
Yg/m
Charging
(1)
0
+ 0.045 kg
+ 0.120 kg
+ 0.195 kg
+ 0.345 kg
15
(2)
Fig.38
Removing the front panel
MW-3000539-01
1
Fig.39
Orifice
MW-3000540-01
2