Baxi Bermuda GF3/LFE5 Super

Fireside Gas Central Heating Units

Installation and 
Servicing Instructions

Please leave these instructions with the user

GF3 Super

LFE5 Super

Summary of Contents for Bermuda GF3

Page 1: ...y www heating spares co Tel 0161 620 6677 Baxi Bermuda GF3 LFE5 Super Fireside Gas Central Heating Units Installation and Servicing Instructions Please leave these instructions with the user GF3 Super LFE5 Super ...

Page 2: ... Gas Baxi Bermuda GF3 Super G C No 37 077 59 Baxi Bermuda LFE5 Super G C No 37 077 61 For use with the following boilers Baxi Bermuda 45 4 M G C No 44 077 71 Baxi Bermuda 45 4 E G C No 44 077 73 Baxi Bermuda 57 4 M G C No 44 077 72 Baxi Bermuda 57 4 E G C No 44 077 74 Baxi Bermuda 51 5 G C No 44 075 06 Renewal Baxi Bermuda GF3 Super Renewal G C No 37 075 01A Baxi Bermuda LFE5 Super Renewal G C No ...

Page 3: ...lation of hot water supplies for domestic purposes BS 5449 Part 1 Forced circulation hot water systems IMPORTANT The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty In GB this could also infringe the GAS SAFETY Installation and Use REGULATIONS Safe Instal...

Page 4: ...standards In GB this is BS 5440 Pt 2 In IE this is I S 813 Domestic Gas Installations The permanent ventilation area size requirements are GF3 LFE5 45 4 69 075cm2 10 7in2 GF3 LFE5 57 4 89 685cm2 13 9in2 GF3 LFE5 51 5 75 45cm2 11 7in2 The permanent vent may be directly into the room containing the appliance The vent may also be sited in another room provided an interconnecting vent is used The vent...

Page 5: ...1 in Min 560mm 22in 406 584mm 16 23in GF3 Super 765mm 301 8in Min LFE5 Super 1015mm 405 64 in Min Fig 2 Wall Fixing Maximum dimensions are strongly recommended Fig 3 Gas Supply Pipe Fireplace Opening Fireplace Opening Skirting Board Hearth Level 100 125mm 4 5in Fig 4 Wall Fixing Support Plate Fire Support Plate Controls Heat Shield Gas Service Tap Extension Panel GF3 Super 765mm 301 8in Min LFE5 S...

Page 6: ...ew ensuring a gas tight seal 9 Test for clearance of flue products as follows a Ensure that all doors and windows are closed IMPORTANT NOTE If there is an extractor or ceiling fan in the room or adjoining room then the spillage test must be performed with the fan turned on and any interconnecting doors between the fan and the appliance left open b Turn on the fire position 4 fully anti clockwise c...

Page 7: ...trols Boiler Manual Controls Boiler Thermostat Knob Service Tap Pilot Viewing Window Fire Control Knob Light Switch Service Tap Levelling Screws Fire Data Label Fig 9 Outer Case LFE5 SUPER Spark Electrode Lead Burner Injectors 2 off Thermocouple Pressure Test Point Sealing Screw Fire Control Tap Fig 10 The Controls GF3 SUPER Control Tap Securing Locknut Tap Fixing Bracket Burner Injectors 2 off Th...

Page 8: ...control knob and light the fire Check that the gas pressure is correct See Commissioning the Fire 15 Test for clearance of flue products as described in paragraph 9 of Commissioning the Fire 16 Refit the outercase control knob 3 pin plug case securing screws and controls cover plate 17 Re check that the ignition is satisfactory Changing Components CAUTION ISOLATE THE ELECTRICAL SUPPLY INCLUDING TH...

Page 9: ... the bracket Undo the thermocouple from the gas tap Remove the assembly from the fire On re assembly shape the thermocouple in a similar manner to the original 7 ELECTRO MAGNET UNIT Figs 10 12 a Remove the gas tap as explained in 1 b b Remove the electro magnet retaining nut and withdraw the electro magnet unit 8 PIEZO UNIT Fig 12 Pull off the plastic cap and disconnect the spark electrode lead fr...

Page 10: ...ply pressure correct 20mb working NO YES NO YES YES NO Has new pilot filter been fitted YES Is spark gap 2 5 to 4mm Adjust spark gap NO YES Is pilot burner clean Is poor flue pull downdraught or blockage evident or flue otherwise unsound Change pilot assembly NO YES Fault Finding Chart BAXI BERMUDA GF3 SUPER LFE5 SUPER Gas Type G20 Natural Gas The thermocouple cannot be changed as an individual co...

Page 11: ...pliance correct NO YES YES YES NO NO NO NO YES YES YES NO YES Are gas cocks fully open Replace both bulbs Does one bulb light Is lead from mains connected Is there 230V across light switch Is there 230V across resistor Are bulbs switched on NO NO YES YES YES YES YES Connect lead Rectify flue Is flue blocked causing A S D to operate YES NO Are pilot flames stable and approx 20mm long Does the fire ...

Page 12: ...4 236204 100 Pilot Filter 205 723 082412 page 12 89 90 BAXI BERMUDA GF3 SUPER B G C No 37 077 59 78 BAXI BERMUDA LFE5 SUPER B G C No 37 077 61 Key No Description G C Manufact rs No Part No 53 Seal Glass Frame 155 747 043111 72 Glass Frame Assembly 155 758 040955 78 Knob Gas Tap Control E01 160 237879 82 Flame Failure Device Gas Tap Concentric TE SA 2324 378 916 238966 83 Encapsulated Unit Concentr...

Page 13: ...6 Existing Fire REMOVING THE EXISTING FIRE Isolate the gas and electrical supply including any permanent live to the combined appliance Remove the controls cover panel from the front of the fire Remove the tap control knob Disconnect the electrical socket from the fire plug if fitted Remove the screws securing the outercase to the innercase Lift off the outercase Turn the gas service tap to the Bo...

Page 14: ...pening using the M5 Nuts and screws provided Use the centre group of holes at each side NOTE If the fire is being used with a Bermuda 401 boiler unit the support brackets from the previous plate must be fitted before the fire support plate can be fixed in place Push the support plate backwards until it touches the surround or wall face and tighten the screws to lock it in position BERMUDA 45 3 57 ...

Page 15: ... hand retaining screw and the left hand coal bed retaining pin which also retains the burner Bermuda GF3 Super Propane 5 64kW 19 243 Btu h G31 Propane P 100 37 0mbar 14 8in wg 35 0 1 7mbar 14 0 0 7in wg Heat Input Gross Gas Group Injector Marking Supply Pressure Setting Pressure Cold The following spares components differ from Natural Gas models Description G C No Manufact rs Part No Flame Failure...

Page 16: ...ing spares co Tel 0161 620 6677 Comp No 237607 Iss 7 1 03 B A X I P O T T E R T O N Brownedge Road Bamber Bridge Preston Lancashire PR5 6SN After Sales Service 08706 096 096 Technical Enquiries 08706 049 049 www baxi co uk ...