NOTE: All Control/Sensor cables are 0.5mm
2
twisted pair (AWG 20). Maximum length 20 metres (shield
grounded at Ambiflo
™
Electrical Heater end only).
* Please note the 5kW Electrical Heater has separate instructions. Please refer to these for details of the
unit and its siting requirements as this can be fitted either to the rear of the Baxi Ambiflo
™
Heat Pump
unit, or sited remotely. Kits are available to hydraulically and electrically connect the 5kW Electrical
Heater to the Ambiflo
™
Heat Pump unit. Please refer to the accessory list on page 5 for kit details and
Fig 1 for details of the kits available for each Ambiflo
™
model.
** The Baxi Programmable Room Sensor must be placed in a secure, tamper proof location where the
temperature does not exceed 25°C. Keep away from sunlight, windows and other heat sources. The unit
needs to be accessible for servicing and should be sited for easy viewing. Please refer to the separate 5kW
Electrical Heater instructions for further details.
Fig. 13
Page 17
4.3 Control Cables from the 5kW Electrical Heater Module
1. The wiring of the 5kW electrical heater contacts must not be routed near power cables in order to avoid
electromagnetic disturbances. Use shielded cable with twisted pairs (shielding grounded on the 5kW
electrical heater side only) - min 0.5mm
2
CSA (Equivalent to AWG 20) 230V Insulation Rated Cable.
2. When extended wire lengths are required between the 5kW Heater and the Heat Pump Unit Baxi
recommends the use of colour coded wiring to reduce the risk of wrongly made connections.
4.4 Main Incoming Fuse
1. This appliance is designed to be fitted to a 100A incoming fuse.
2. A free upgrade service is available from your local utility company where the infrastructure will
support this. Please contact your regional supplier for further information. Your electricity utility bill will
give a helpline number.
4.5 Electrical Diversity
1. This appliance is designed to be fitted to a 100A incoming fuse. This fuse is fitted to main cable
incoming to the house and the rating (a number) is given on the side.
2. If the incoming fuse is not rated at 100A contact your power network provider who will be able to
upgrade your fuse (Section 4.4 paragraph 2) where this is not possible see Section 4.5 paragraph 5.
3. Baxi recommends, a suitably qualified and competent electrician should undertake the task of
electrically connecting the Ambiflo
™
Heat Pump.
4. Baxi recommend that a diversity of load assessment must be carried as suggested by IEE to be within
the best practice guide lines. The current demand of the house is determined by adding the current