29
© Baxi Heating UK 2012
11.0
Commissioning of solar controller
0
Anro
6
Tyfocor L5.5 - supplied
1
IIexan E, Glythermin
7
Dowcal 10
2
Antifrogen L
8
Dowcal 20
3
Antifrogen N
9
Dowcal N
4
IIexan E
10
Tyfocor LS
5
IIexan P
11
Fernox S1
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?
11.6
Menu “Basic adjustment”
1. Adjustment and changes in this menu must be carried out
only by a competent installer or service engineer.
Incorrect adjustments may adversely affect the function of
controller and solar primary system.
2. To avoid accidental changes in menu “Basic adjustment”, it is
not editable in normal functioning but has only a display
function. To be able to carry out any changes, this menu must
be chosen within the first minute after switching on the
appliance.
The basic adjustment menu is ‘blocked’
automatically one minute after switching on if the menu is
not accessed.
For correct operation of the system, Baxi
recommend the settings shown above.
Indication
Collector protection function
110..150°C
120°C
Recooling storage tank temperature
30..90°C
40°C
Energy yield measurement 'Off'
0
Energy yield measurement
with flow meter
1
Energy yield measurement
without flow meter
2
Energy yield measurement -
sets glycol type
0…11
11
0 ... 100%
5% - steps
No value shown, when item 5 is set to 0
-----
Adjustment value when item 5 is set to 1
0.5 – 25Litres
per impulse
Adjustment value when item 5 is set to 2
0.1 – 75Litres
per minute
First priority storage tank selection
1 - 2
1
12 -- 6
Anti-freeze function.
Reference sensor selection
1 - 6
6
30 - 480
11 -- 0
Antifreeze function
0 = off
1 = on
0
10 -- 1
100
9 -- 240
Multiple tank storage systems.
Controller response time in seconds
240
8… 10
10
6 -- 11
7 -- 100
Energy yield measurement -
glycol mixture
5 -- 2
3 -- 40 °C
4 -- 0
Tube collector function - time-controlled
0
0 = off
1 = on
2
0 -- 0
0
1 -- 120 °C
2 -- 0
Recooling function
(only if the collector protection is on)
0
Collector protection function
0 = off
1 = on
0 = off
1 = on
Description
Value range
Factory
set - up
Line / value
Note: This Solar Controller has
the ability to calculate the
energy yield without the use
of a flow meter. The Flow
Meter is now available as an
accessory - Code no. 5122979.
Anti-freeze function start temperature
-20 °C ... +7 °C
3
0 = off
1 = cooling
2 = thermostat
1 - 6
5
16 -- 0
System diagram
0 - 4
0
15 -- 5
Independent controller reference sensor
2
13 -- 3°C
14 -- 2
Independent controller function
Fig. 32