3.
Specifications
3.1
Environmental
•
Operation temperature range : -30 ~ +70 °C (*)
(*)
The embedded GSM/GPRS module remains fully functional during
after this temperature exposure ; and shall meet the minimum
requirements of 3GPPP or appropriate standards.
•
Storage temperature range : -40 ~ +85 °C
•
Relative humidity (non condensing) : 85% maximum
•
IP class : IP20
3.2
Housing
The
DinBox RTU M4
is enclosed into a Phoenix UEG-EU-BE housing.
This housing has a DIN rail snap slot for easy DIN rail mounting.
dimensions
172 mm x 35 mm x 135 mm
3.3
Power Supply
AC Power Supply
Input voltage range
85 ~ 264 Vac / 120 ~ 370 Vdc
Frequency range
47 ~ 440 Hz
Safety standards
EMC, UL1950, TUV EN60950
Withstand voltage
3 KVac
DC Power Supply (optional)
Input voltage range
9 ~ 26 Vdc
Polarity protected with diode
No internal fuse