Appendix A.
IEC60870-5-104 information overview
The address map for the
DinBox RTU M4
is as follows:
Object
Object type description
Type IOA
Interrogation Command
100
-
Clock sync command
103
-
Battery input
Measured Value, Short Floating Point number
with time tag (MME C)
36
400
CSQ input
Measured Value, Short Floating Point number
with time tag (MME C)
36
408
Analog input 1
Measured Value, Short Floating Point number
with time tag (MME C)
36
420
Analog input 2
Measured Value, Short Floating Point number
with time tag (MME C)
36
421
Digital input 1
Single-Point information with time tag (MSP)
30
520
Digital input 2
Single-Point information with time tag (MSP)
30
521
Digital input 3
Single-Point information with time tag (MSP)
30
522
Digital input 4
Single-Point information with time tag (MSP)
30
523
Digital input 5
Single-Point information with time tag (MSP)
30
524
Digital input 6
Single-Point information with time tag (MSP)
30
525
Digital input 7
Single-Point information with time tag (MSP)
30
526
Digital input 8
Single-Point information with time tag (MSP)
30
527
Mains disconnect
Single-Point information with time tag (MSP)
30
528
IOA Modbus failed
Single-Point information with time tag (MSP)
30
530
Digital output 1
Single Command with time tag
58
600
Digital output 2
Single Command with time tag
58
601
Map download trigger
Single Command with time tag
58
6000
Map download status
Measured Value, Short Floating Point number
with time tag (MME C)
36
6001
IOA clear Modbus failed
Single Command with time tag
58
6010
Modbus read
Single Point information (MSP)
1
map
Modbus read
Bitstring of 32 bits (MBO)
7
map
Modbus read
Measured value, normalized value (MME-A)
9
map
Modbus read
Measured value, scaled value (MME-B)
11
map
Modbus read
Measured value, short floating point number
(MME-C)
13
map
Modbus write
Single command (CSC)
45
map
Modbus write
Double command (CDC)
46
map
Modbus write
Set point command, normalized value (SCE-A)
48
map
Modbus write
Set point command, scaled value (CSE-B)
49
map
Modbus write
set point command, short floating point number
(CSE-C)
50
map
See the
DinBox RTU M4
CI Guide document for more information about the used ASDU
and ASDU types. The IOA of the different ASDU's can be freely changed, see next
chapters.