Cable requirements
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
44
6.4
In case UL 508 C is considered: the maximum short-circuit current of the supply may be
10000 A.
A listing of the requirements to the electrical supply is to be found in
h
Assure, that the existing supply fulfills all requirements.
6.4
Cable requirements
In the technical specifications, see (
Appendix D - Technical specifications
97) you will find all data, e.g. environmental conditions, electrical connection data and oth-
er which must be observed when choosing a cable. The BUM64S/A/F unit meets the UL
requirements, if you use the respective cables and if you carry out the fastening of the
cables accordingly.
Further information you will find in the appendix under
Cable for control voltage supply / signals
h
make sure that all cables used meet the requirements.
6.5
Connections
In the following we give you detailed information about the connections. A summary is
shown in the
NOTE
If UL508C is applied:
connect only 60 °C / 75 °C copper lines. Carry out the fastening of the
power connections with the correct torque, see also information given in