Cable from mains supply to appliance
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
104
D.8
D.8
Cable from mains supply to appliance
1)
EN 60204-1, tab. 5, attachment form C
For UL-conform machines/plants you must use UL-certified cables.
2)
Mount max. 2 cable lugs per power rail. Do not mount cable lugs onto each other, mount one on each side of the power rail.
Use cable lugs that have a maximum width of 25 mm. Keep in mind that the M10 screw is used for attachment.
D.9
Cable for control voltage supply / signals
Cross-section
1)
depending on mains current
Maximum length mains to mains filter
user-defined
Maximum length mains filter to mains reactor
max. 0.3 m (unscreened)
max. 5 m (screened)
Maximum length mains reactor to unit
max. 0.3 m (unscreened)
max. 5 m (screened)
Cable lug / end sleeve, connection to unit
2)
cable lug
Cross-section
2 x 0.2 to 2.5 mm
2
(w/o end sleeve)
2 x 0.25 to 2.5 mm
2
(with end sleeve)
Maximum length
any
End sleeve, connection to appliance
flexible, with or without end sleeve