Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
99
3
The cold slip frequency must be lower than the warm slip frequency (
).
At asynchronous motors without an electronic type plate the parameter must be set man-
ually.
107.16
Slip frequency
(
warm)
(this is relevant at asynchronous motors with encoder, only)
Slip frequency of the motor at nominal torque current and nominal flux (magnetic flux =
100%) according to the slip temperature (warm)
. The parameters
107.16
and
support the temperature adaption characteristic of the slip frequency. Refer to
"Slip frequency temperature actual value"
.
The slip frequency when warm must be higher than the slip frequency when cold
(
At asynchronous motors without an electronic type plate the parameter must be set man-
ually.
107.17
Slip temperature (cold)
(this is relevant at asynchronous motors with an encoder if the temperature monitoring is
activated,
bit 0 to 7).
Temperature specification for which the motor slip frequency when cold (
) ap-
plies, see also
.
The cold slip temperature must be lower than the warm slip temperature (
).
At asynchronous motors without an electronic type plate the parameter must be set man-
ually.
107.18
Slip temperature (warm)
(this is relevant at asynchronous motors with an encoder if the temperature monitoring is
activated,
bit 0 to 7).
Temperature specification for which the motor slip frequency when warm (
) ap-
plies, see also
.
The slip temperature when warm must be higher than the slip temperature when cold
(
At asynchronous motors without an electronic type plate the parameter must be set man-
ually.