Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
110
3.4
Details about the standardization modes in the torque current limits are described in the
chapter
Bit 5
:
By default, the adaption is not active due to compatibility reasons. It is recommended to
activate the adaption if the breakdown torque limit (
138.1
Bit 2 = 1) is activated.
138.2
Iq limit motor/TD1
This parameter limits the torque current set value for the motor operation or in the torque
direction 1 (depending on setting in
bit 0).
The parameter is subject to the hysteresis (
) when defining the quadrant.
Other torque current limits are available, as well:
and the
torque current limit generated the torque limit
Furthermore, there are other torque limits
,
and
.
In addition, the motor-operated torque current can be disabled due to power failure (refer
to
The strongest limit is effective. The definite upper and lower torque current limit is dis-
played in
Standardization:
100%
=
Max. torque current
138.3
Iq limit generator/TD2
This parameter limits the torque current set value for the generator operation or in the
torque direction 2 (depending on setting in
bit 0).
The parameter is subject to the hysteresis (
) when defining the quadrant.
Other torque current limits are available, as well:
and the
torque current limit generated the torque limit
Furthermore, there are other torque limits
- and
. In addition, the motor-operated torque current can be disabled due to power failure (refer
to
The strongest limit is effective. The definite upper and lower torque current limit is dis-
played in
Standardization:
100%
=
Max. torque current