4.7.4.3 Description of the Field Weakening parameters
142.1
Field Weakening Mode
142.2
Field weakening factor
The field weakening factor represents the current level of the field weakening.
The field weakening factor is without units. The range of values extends from 0 to 1.
The field weakening factor accords to the minimum value between field weakening output
and the field weakening factor after the speed
142.7
Actual filtered output voltage
RMS
FLOAT
0
1000
0
V
1:1
X
142.8
Voltage threshold for field
weakening
FLOAT
50
600
600
V
1:1
X
142.9
Speed threshold for field
weakening
FLOAT
10
500000
3000
U/min
1:1
X
142.12
Field controller due to speed FLOAT
0
1
1
1:1
X
142.13
Field weakening controller
output
FLOAT
0
1
1
1:1
X
142.15
Factor field weak threshold
FLOAT
0
1
1
1:1
X
X
142.19
P-Gain breakdown torque
controller
FLOAT
0
1000
0.001
1/V
1:1
X
142.20
Integral action time break-
down torque control
FLOAT
0.001
10000
20
ms
1:1
X
142.21
Factor breakdown torque
threshold
FLOAT
0
1.15
1.02
X
X
142.22
Breakdown torque control
output
FLOAT
0
1
1
1:1
X
Bit
Meaning
0
Field weakening type:
0: "At the voltage limit": Field weakening via the field weakening factor
.
1: "Permanent field current": Isd set value (
) = Field current preset
value (
)
Other details see
1
Threshold speed of the controlled field weakening characteristic:
0: Motor nominal speed (
).