LED display BM5030 with safety function
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
Baumüller Nürnberg GmbH
306
C.4
C.4
LED display BM5030 with safety function
BM5030-XX2X-...
LED
H1
READY - Mains rectifier unit ready-to-operate:
green
:
Power supply and DC link voltage available, internally
OK
red
:
Power supply failure - automatically restart when power
supply returns.
blinking red:
Power supply failure longer than 10 s - restart after
Power supply return has to be acknowledged (X1:4).
Refer to
Error acknowledgment of BM50XX
LED
H2
PHASE FAILURE
red
:
Phase failure
LED
H3
OVERTEMPERATURE
red
:
Overtemperature
LED
H4
DC-LINK ERROR
red
:
DC link error:
U
DC link
overvoltage or
U
DC link
overcurrent or
Inhibit input active
LED
H5
LED
H6
STO POWER
green
:
U
DC
is available
orange
:
U
DC
is not ready
red
:
Error
STO STATUS
green
:
Ready-to-operate
orange
:
U
DC link
charging procedure,
red
:
STO error
Figure 127:
Display/operating elements BM5030-XX2X-...