Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
119
4
P1187
Status for ramp function generator.
P1188
This parameter displays the frequency output of the ramp function generator.
P1189
The multi-function input terminals MI3 to MI5 or MI7 to MI12 (refer to
to
and
) are used to select one of the b maXX
®
1000 multi-
step speeds. The speeds (frequencies) are determined by
P1190
The multi-function input terminals MI3 to MI5 or MI7 to MI12 (refer to
to
and
) are used to select one of the b maXX
®
1000 multi-
step speeds. The speeds (frequencies) are determined by
P1187
Hochlaufgeber Status
0 to 65535
-
Ramp function generator status
0
A
BM_u_RFGStatus
1:1
Bit
Meaning
0 to 3
reserved
4
1: RFG output is internally set to 0 (RFG inhibit)
5
1: RFG is stopped on the ramp (RFG stop)
6
1: RFG input is internally set to 0 (RFG zero)
7
1: Quickstop ramp is active (RFG quickstop)
8
1: Ramp-up is active
9
1: Ramp-down is active
11 ... 10
reserved
12
1: RFG output = RFG input (set value reached)
P1188
HLG Ausgang
0.00 to 600.00 Hz
-
RFG output
0.00 Hz
A
BM_u_RFGOutput
100:1
P1189
1. Stufengeschwindigkeit
0.00 to 600.00 Hz
EE
1st step speed frequency
0.00 Hz
ON
BM_u_1StepSpeedFrequency
100:1
-
P1190
2. Stufengeschwindigkeit
0.00 to 600.00 Hz
EE
2nd step speed frequency
0.00 Hz
ON
BM_u_2StepSpeedFrequency
100:1
-