NE230
34
www.baumer.com
To read
To change
Preset value P2
➜
Press the
key.
The preset value P2 can be read off in the display.
LED “P2“ flashes.
➜
Enter preset value P2 with keys
and
.
Sign possible following release in line 38
➜
Press the
key.
To read
To change
Start count SC
➜
Press the
key.
The current start count SC can be read off in the display.
LED “SC“ flashes.
➜
Enter start count SC with keys
and
.
Sign possible following release in line 38
➜
Press the
key.
To read
Totalizer ∑
➜
Press the
key.
The current total value can be read off in the display.
LED „∑“ flashes.
If the value 999999 is exceeded, its display will be shown in two
steps.
First step: Display of the first 6 digits.
Second step, marked by „H“: Display of 7
th
and 8
th
digits.
Display of each value for approx. 3 seconds.
Reset
➜
Press the
key.
To read
Reset
Hour counter „ “
➜
Press the
key.
The hour counter can be read off in the display.
LED „ “ flashes.
➜
Press the
key.
To read
To change
Scaling factor SF
➜
Press the
key.
The current scaling factor SF can be read off in the display.
➜
Enter scaling factor SF with keys
and
.
➜
Press the
key.
The scaling factor allows the display of fractions or multiples of the
counting pulses. Setting range: 0.0001 to 9999.99. Setting ex factory
1.0000
Example
In the case of a length measurement by means of encoder and
cyclometer, where the circumference of the cyclometer measures
200 mm and the encoder supplies 500 pulses per revolution, the
measurement is to be displayed in mm. The scaling factor is calcula-
ted as follows:
Scaling factor =
Circumference
=
200
= 0.4000
Pulses
500
By pushing
again, the current counter status is re-displayed.