Parameter values of parameterization function (Set_Prm)
Parameter
Data
type
Octet
Nr.
Value range
Default parameter
in GSD file
Station status
Octet
string
1
Sync and freeze
mode supported
Supported baud
rates
Response monitoring
time
Octet
string
2 to 3
Profibus-specific data
Minimum Station Delay
Responder
Octet
string
4
Depending on Baud
rate
Ident No.
Octet
string
5 to 6
059B
Group Ident No.
Octet
string
7
00
Operating parameter
Octet
string
8
Profibus-specific data
Parameters of the
inclination sensor
Octet
string
9
Bit 0 = 0/1 inversion X-axis
Bit 1 = 0/1 inversion Y-axis
Bit 2 = 0/1 scaling X-axis
Bit 3 scaling Y-axis
Bit 4 = 0/1 standard
diagnosis/ extended
diagnosis
less inversion
less inversion
less scaling
less scaling
extended
diagnosis
Resolution
Octet
string
10
0x00 to 0x03
0x00 = 0.001° Resolution
0x01 = 0.01° Resolution
0x10 = 0.1° Resolution
0x11 = 1.0° Resolution
Default = 0x10 = 0.1°