Baumer G0AMH Manual Download Page 9

 

Baumer_ProfibusDPV0_BIDE_MA_EN.docx 

9/26 

Baumer IVO GmbH & Co. KG 

11.19 

 

Villingen-Schwenningen, Germany 

6. 

Data exchange between Profibus-DP devices 

6.1.

 

Telegram structure 

The diagram illustrates the telegram structure. 
 

Telegram structure 

 

DP Master 

Triggering telegram 

 
 
DP Slave 

Footer info 

Output data 

Header info 

 

Reply telegram 

Header info 

Input data 

Footer info 

 

 
 

6.2.

 

Initialization, restarting and user data communication 

Before an exchange of useful information between the master and slave, every slave is re-initialized. The 
master transmits parameterization and configuration data to the slave. Only when the parameterization and 
configuration data is in agreement with the data stored in the slave can user data be exchanged. This takes 
place in the following way: 
 

Diagnostic request from the master 

The master transmits a Diagnosis Request to a slave (Slave_Diag), and the slave responds with a Slave 
Diagnosis Response. 
The master uses this data to check whether the slave exists in the bus and is ready for parameterization and 
configuration.  
 

Parameterization of the slave 

The master transmits a Parameter Request to the slave (Set_Prm).

 

The Slave receives information about the current bus parameters, surveillance times and slave-specific 
parameters via the parameterization data. The parameters are taken over during the project processing 
phase partially directly or indirectly from the GSD file. The slave compares this parameterization data with its 
own stored data.  
 

Configuration of the slave 

The master transmits a Check Configuration Request (Chk_Cfg).

 

The master informs the slave of the scope (number of data bytes) and the structure (data consistency) of the 
input and output ranges to be exchanged. The slave compares this configuration with its own configuration. 

 
Diagnosis request prior to data exchange 

The master transmits another Slave Diagnosis Request (Slave_Diag), the slave answers with a Slave 
Diagnosis Response. 
The master now checks whether the parameterization and configuration agree with the data stored in the 
slave. If the data requested by the master is admissible and if no error exists, the slave signals its readiness 
for the transfer of user data by means of the diagnosis data.  
 

Data_Exchange 

The slave now responds exclusively to the master which has parameterized and configured it. 
The master transmits a user data request (Data_Exchange), the slave answers with a user data response. In 
this response, the slave informs the master whether current diagnosis results are available. The slave only 
makes known the actual diagnosis and status information after the master's diagnosis telegram. 
 

Summary of Contents for G0AMH

Page 1: ...ingen Phone 49 7720 942 0 Fax 49 7720 942 900 11 19 174 02 024 9 info de baumerivo com Subject to modification in technic and design www baumer com Errors and omissions excepted Manual Absolute Encode...

Page 2: ...data communication 9 7 Parameterization and configuration 10 7 1 Parameterization 10 7 2 Configuration 13 8 Diagnostic signals 14 8 1 Description of the diagnosis data Slave_Diag 14 8 2 Parameter val...

Page 3: ...demarks SIEMENS SIMATIC Step7 und S7 are registered trademarks of Siemens AG PROFIBUS the PROFIBUS Logo and PROFIdrive are registered trademarks of the PROFIBUS user organization respectively of PROFI...

Page 4: ...ultivoPlus Multiturn GBLMS GBMM059B gsd multivoPlus Multiturn GCAMS GCAM059B gsd magtivo Singleturn GCMMS GCMM059B gsd magtivo Multiturn GXAMS GXAM059B gsd multivo Singleturn GXLMS GXMM059B gsd multiv...

Page 5: ...with a suitable coupling Hollow shaft Open clamping ring completely before mounting the encoder Foreign objects must be kept at a sufficient distance from the stator coupling The stator coupling is n...

Page 6: ...erface Available bus interfaces CANopen DeviceNet EtherCAT Ethernet IP Profibus DP Profinet Powerlink Power over EtherCAT SAE J1939 SSI All encoders enable parameterization by bus interface Functional...

Page 7: ...lass 1 or class 2 The Profibus DP is characterized by the following features Short response times 1 ms with 32 users and 12 MBaud Reliable transmission procedure Hamming distance 4 Availability of a w...

Page 8: ...t in integral steps Measurement range Total resolution number of steps per revolution x number of revolutions input in integral steps Preset value A certain output value is assigned to the current pos...

Page 9: ...eillance times and slave specific parameters via the parameterization data The parameters are taken over during the project processing phase partially directly or indirectly from the GSD file The slav...

Page 10: ...mode active Response monitoring active Master assigned 1 Response monitoring time 2 to 3 Recognition of master failure master must respond within this period 1 Min station delay responder tsdr 4 Mini...

Page 11: ...dent no Octet string 7 00 1 Operating parameter Octet string 8 Profibus specific data 1 Operating parameter Octet string 9 Bit 0 0 1 CW CCW Bit 1 0 1 Device class 2 off on Bit 3 0 1 Scaling function o...

Page 12: ...r shaft may rotate unlimited when encoder not powered How to determine if Endless Operation is in use Multiply the encoder s max possible revolutions depending on encoder 16 bit 65536 or 13 bit 8192 b...

Page 13: ...1h 2 words input data with data consistency for position values to max 31 bit 2 F1h 2 words output data with data consistency for preset value to max 31 bit 2 words input data with data consistency fo...

Page 14: ...atus 1 1 Status of Parameterization Configuration Diagnostic data Diag ext bit and Diag stat bit in case of alarm and warning signals 1 Station status 2 2 Status of Response monitoring Freeze or Sync...

Page 15: ...cribed value only multiturn encoders 2 Profile version 24 25 Profile version of the encoder profile in revision number and index 2 Software version 26 27 Indicates the software version in revision num...

Page 16: ...lithium cell supplies the necessary supply voltage for the part of the circuit necessary for counting revolutions and storing them in the ASIC When the operating voltage is switched on the stored valu...

Page 17: ...ivoPlus 2 Additional alarm signals Octet string 17 Not supported 2 Supported alarm signals Octet string 18 19 Octet 19 Bit 0 1 Position error supported 2 Warnings Octet string 20 21 Octet 21 Bit 5 1 L...

Page 18: ...in the programmed overall measurement range To ensure optimum coordination between the mechanical position and the preset value the preset value should only be set when the encoder is at a standstill...

Page 19: ...t must be separated beforehand using the formula described below and then recalculated A calculator with hexadecimal function of the type provided among the Windows accessories is helpful here Convers...

Page 20: ...Baumer_ProfibusDPV0_BIDE_MA_EN docx 20 26 Baumer IVO GmbH Co KG 11 19 Villingen Schwenningen Germany Example for entering parameters...

Page 21: ...nt with rubberized spring element Push the encoder on to the drive shaft and insert the parallel pin into the mounted adjusting element not supplied with rubberized spring element Adjusting bracket Pu...

Page 22: ...ip the cable sheath and cores shorten the shield film where this exists see Fig Bend over the braided screen by approx 90 Push the sealing insert with contact sleeve along as far as the braided shield...

Page 23: ...Baumer_ProfibusDPV0_BIDE_MA_EN docx 23 26 Baumer IVO GmbH Co KG 11 19 Villingen Schwenningen Germany Bus cover shaft end shaft 1 2 3 Cable gland M12 connector Bus cover hollow shaft G1 and G2 1 2 3...

Page 24: ...o the 8 pin terminal block inside the interface converter The additional functions Zero and UP DOWN provided by the encoder are to be assigned as follows for optimum interference immunity Zero additio...

Page 25: ...ity of 100 nH Carefully plug the bus cover onto the D SUB plug of the basic encoder then press only via the sealing rubber taking care not to tilt it The bus cover must rest fully against the basic en...

Page 26: ...s With cable type A all transmission rates up to 12 MBaud can be used Features Data Shaft resistance in Ohm 135 to 165 at 3 to 20 MHz Operating capacity pF m Less than 30 Loop resistance Ohm km Less t...

Reviews: