Operating instructions 
CleverLevel switch, LFFS 

 Mounting 

www.baumer.com 

Operating instructions: 11109132 09 EN      Page 3 / 20 

NOTE 

 

The M12 cable rotating nut must be tightened by hand force only. 
Max. torque is 0.6 Nm. Do not use any tool. 

Refer to www.baumer.com for O-rings, gaskets and other accesso-
ries. 

If the PEEK sealing rings for sliding connection is damaged or seri-
ously scratched, the instrument or sealing rings should be replaced 
(type ZPX1-006). 

1) Use only a 3-A approved counterpart. 

2) The leak detection port should be visible and drained. 

3) Mount the adapter in a self-draining position/angle. 

4) Level the inner surface of the pipe with the counterpart. 

After installation: 

 

Check the leak tightness of the sleeve. 

 

Check the tightness of cable glands or M12 plug. 

Example        
with ZPW2-626 

 

 

 

 

 

Example with 
ZPW3-321 

Example with 
ZPW2-621 

 

Leak detection port

 

must be placed at the 

 

lowest possible position.

 

Fitted 
incorrectly  

Cannot be 
drained 

WARNING 

5) The 3-A mark or the arrow shall be placed upwards. 

6) Welding should be grinded to Ra ≤ 0.8. 

7) Tighten the instrument in the adapter with a torque of 15...20 Nm. 

If the seal is leaking and the media appears in the leak detection 
port, the seal is to be changed immediately. 

Before reassembly, clean the hole and inside of the connection with 
detergent and sanitising liquid. Use a small brush. Verify that all of 
the inside area is completely clean. 

Reassemble and verify that the connection is tight. 

Do not use Teflon, elastomer or other types of gaskets for the hy-
gienic process connection featuring a conical seal. 

The industrial versions with thread must be sealed e. g. by gasket or 
Teflon® tape and tightened into the counterpart.  

Installation of hygienic 3-A approved and EHEDG certified products, 
please refer to below: 

The switch provides IP67 protection in cable version or if installed 
with IP67-compliant M12 cable. Switch installation using an IP69K 
cable ensures IP69K conformity. 

Stainless 
steel tube 

NOTE

 

The CleverLevel switch is to be mounted in a closed metal pipe, tank 
or container.  

Summary of Contents for CleverLevel LFFS-1 Series

Page 1: ...ption The Level Switch LFFS designed to detect levels in tanks media separation and provide empty pipe detection or dry run protection for pumps By means of the FlexProgrammer 9701 the output can be configured to either NPN PNP or digital output signal A damping of the output signal can be activated in case of a fluctuating media level e g during tank filling The measurement is precise and unaffec...

Page 2: ...Mounting instructions for sliding connection 1 Clean the sliding shaft 2 Mount the smallest ring against the media as indicated 3 Tighten the G1 2 Hygienic sliding nipple at 25 30 Nm 4 Replace the Washer ring kit when one or both parts are permanently deformed or stick to the shaft of the sliding connection The Level Switch LFFS with sliding connection can be mounted in installations with a static...

Page 3: ...ly Cannot be drained WARNING 5 The 3 A mark or the arrow shall be placed upwards 6 Welding should be grinded to Ra 0 8 7 Tighten the instrument in the adapter with a torque of 15 20 Nm If the seal is leaking and the media appears in the leak detection port the seal is to be changed immediately Before reassembly clean the hole and inside of the connection with detergent and sanitising liquid Use a ...

Page 4: ... DN 40 ZPH3 3254 for tank tube DN 50 ZPH3 3255 ZPW2 324 Adapter Welding EH FTL to pipe extrusion G A ZPH1 32BA DN 25 DN50 ZPW2 326 G1A ZPH1 32CB DN 65 DN150 ZPW2 327 VS G A ZPH1 32BC G1A ZPH1 32CD Adapter Adapter industrial Adapter industrial G G1 G G1 ZPI1 32B Sliding connection ZPH1 32C0 G G1 ZPI1 32D G G DIN 3852 E G G2 ZPI1 32E ZPI1 32A Welding for tank ZPW2 621 Welding for pipe end ZPW2 626 w...

Page 5: ...ank with a total in sertion length of 130 mm Hence the external length of the sliding connection will be 250 130 120 mm The media temperature will be max 160 C Read the x axis at 120 mm and the y axis at 160 C and find that the ambient temperature must be kept below 60 C In case the radiated heat from the tank will cause a higher ambient temperature at the housing efficient insulation of the tank ...

Page 6: ...ight on for 2 seconds Register full state stores the value and returns to Normal operation with new setting NOTE If the media is sticky foamy powdery or in other ways leaving parts of the media at the sensor tip this situation has to be estab lished also during the Teach In process Otherwise a faulty calibration can be the result If Teach In for some reason do not succeed the CleverLevel Switch LF...

Page 7: ...ed 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 www baumer com Operating instructions 11109132 09 EN Page 7 20 Active Low NPN and Digital output VDC 2 5V 0 5V Rload 1 kΩ Active High PNP and Digital output VDC 2 5V 0 5V Rload 1 kΩ ATEX Connection type Ambient temperature Media temperature max allowed Note G hygienic 40 85 C 85 C 3A DN38 40 60 C 95 C 1 40 40 C 115 C 1 100 mm 40 85 C 85 C Sliding connection 4...

Page 8: ... product must be installed in accordance with prevailing guidelines for zone 20 without a barrier Ex data Supply range VDC 12 5 30 Load I 0 1 A Temperature class T1 T5 Pls see table top page 7 12 5 30 1 2 5 ATEX Gas nA A Level Switch LFFS 3xx x is Ex nA II T5 ATEX II 3G approved for application in hazardous areas in accordance with the current EU directives The product must be installed in accorda...

Page 9: ...net sich hervorragend für die Füllstandserkennung in Behältern die Medientrennung sowie die Erkennung leerer Rohre und den Trockenlaufschutz von Pumpen Mithilfe des FlexProgrammer 9701 kann der Ausgang als NPN PNP oder ein digitales Ausgangssignal konfiguriert werden Im Falle eines veränderlichen Medienfüllstandes z B während der Befüllung des Behälters kann eine Dämpfung des Ausgangssig nals akti...

Page 10: ...werden Bitte keine Dichtungen aus PTFE Fasern oder sonstige Dich tungen verwenden Wenn sich die aus PEEK bestehende Spit ze gegen die Einschweissmuffe aus Edelstahl drückt bildet dies eine hygienegerechte Dichtung vorausgesetzt die Richtli nien wurden befolgt Aufgrund des Messprinzips ist es wichtig dass für die Sensor spitze ein ausreichend grosses Stück von Metallachse oder Einschweissmuffe sich...

Page 11: ...3A Markierung bzw der Pfeil sollte nach oben zeigen 6 Schweissnähte sollten so abgeschliffen werden dass sie einen Wert von Ra 0 8 aufweisen 7 Gerät im Adapter mit einem Drehmoment von 15 20 Nm festzie hen Wenn die Dichtung undicht ist und die Medien in der Kontrollbohrung sichtbar werden muss die Dichtung sofort ausgetauscht werden Vor dem erneuten Zusammenbau die Bohrung und das Innere des Ansch...

Page 12: ...254 für Behälter Rohr DN 50 ZPH3 3255 ZPW2 324 Adapter Einschweissmuffe EH FTL für Rohr mit Auszug G A ZPH1 32BA DN 25 DN50 ZPW2 326 G1A ZPH1 32CB DN 65 DN150 ZPW2 327 VS G A ZPH1 32BC G1A ZPH1 32CD Adapter Adapter Industriell Adapter Industriell G G1 G G1 ZPI1 32B verschiebbarer Anschl ZPH1 32C0 G G1 ZPI1 32D G G DIN 3852 E G G2 ZPI1 32E ZPI1 32A Einschweissmuffe für Behälter ZPW2 621 Einschweiss...

Page 13: ...von 130 mm in einen Tank montiert Seine externe Länge beträgt daher 250 130 120 mm Die Medientemperatur beträgt max 160 C Liest man den Schnittpunkt aus 120 mm auf der X Achse und 160 C auf der Y Achse ab so ergibt sich dass die Umgebungs temperatur unter 60 C gehalten werden muss Falls die Abstrahlwärme vom Behälter zu einer höheren Umgebungs temperatur am Gehäuse führt muss für eine wirksame Iso...

Page 14: ...rz an VDC anschliessen Leuchtet 2 Sekunden lang Registriert den Zustand gefüllt speichert den Wert und kehrt mit den neuen Einstellungen zum Normalbetrieb zurück ANMERKUNG Bei klebrigen schäumenden pulvrigen oder anderen Medien von denen leicht Reste an der Sensorspitze haften bleiben müssen diese Bedingungen auch während des Teach In Verfahrens vorliegen Andernfalls kann die Kalibrierung fehlerha...

Page 15: ... Schliesser NO Öffner NC Elektrische Daten Spannungsversorgung 12 5 36 VDC 35 mA max Ausgang PNP NPN oder Digital Max 50 mA kurzschlussfest und hochtemperaturfest Low aktiv NPN und digitaler Ausgang VDC 2 5V 0 5V Rload 1 kΩ High aktiv PNP und digitaler Ausgang VDC 2 5V 0 5V Rload 1 kΩ 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 www baumer com Betriebsanleitung 11109132 09 DE Page 15 20 PNP Ausgang NPN Aus...

Page 16: ...C 1 100 mm 40 85 C 85 C verschiebbarer Anschluss 40 60 C 155 C 1 40 40 C 175 C 1 250 mm 40 85 C 85 C verschiebbarer Anschluss 40 60 C 195 C 1 40 40 C 200 C 1 Bedingungen für Ex Zertifizierung 1 Gilt unter der Voraussetzung dass die Sensor spitze am Gerät als einziges Teil mit dem Medium in Berührung ist ATEX Gas ia LFFS 1xx x mit PNP Ausgang Safe area 22 120 VDC or 90 253 VAC ANMERKUNG Bei PNP Aus...

Page 17: ...Produkt ist gemäss den üblichen Richtli nien für Zone 2 ohne Barriere zu installieren Ex Daten Spannungsversorgung VDC 12 5 30 Last I 0 1 A Temperaturklasse T1 T5 Siehe Tabelle oben auf Seite 16 Der FlexProgrammer 9701 darf in der gefährlichen Umgebung nicht an den Füll standsschalter LFFS angeschlossen werden Vorgehensweise bei der Konfigurierung a Netz vom 4 20 mA Regelkreis trennen b Füllstands...

Page 18: ...WHG leakage and overfill protection approval Betriebsanleitung CleverLevel switch LFFS www baumer com Betriebsanleitung 11109132 09 DE Page 18 20 ...

Page 19: ...Betriebsanleitung CleverLevel switch LFFS www baumer com Betriebsanleitung 11109132 09 DE Page 19 20 WHG leakage and overfill protection approval ...

Page 20: ...www baumer com Betriebsanleitung 11109132 09 DE Page 20 20 For further information please refer to www baumer com ...

Reviews: