 Mounting 

Operating instructions 
CleverLevel switch, LFFS 

Please refer to “Accessories” data sheet. The welding part has 
an engraved mark or a leak hole. When the product has been 
mounted and correctly tightened the gland or M12 plug will 
align with this mark.  

Make sure that the gland/plug is pointing downwards to pre-
vent fluids from penetrating into the instrument. 

Use only the authorised special designed accessories. The 
product warranty is void when installed with other adapters. 

Do not use PTFE, fibre or other gaskets. The PEEK tip against 
the stainless steel welding part will perform a hygienic tighten-
ing provided that the guidelines have been followed. 

Due to the measuring principle it is essential that the sensor tip 
can “see” an ample amount of the metal shaft or welding part. 

 

Dimensions

 

Mounting instructions for sliding connection: 

1) Clean the sliding shaft. 

2) Mount the smallest ring against the media as indicated. 

3) Tighten the G1/2 Hygienic sliding nipple at 25...30 Nm. 

4) Replace the Washer ring kit when one or both parts are 
  permanently deformed or stick to the shaft of the sliding    
  connection. 

 

 

 

The Level Switch LFFS with sliding connection can be mounted 
in installations with a static pressure up to 16 bar. 

To prevent personal injuries or property damage it is essential 
that the safety wire is mounted correctly and is undamaged. 

WARNING 

Compression ring kit 
ZPX1-006 for sliding 
version 

              G 1/2 A hygienic sliding connection 

    BHC 3A DN38 hygienic 

             G 1/2 A hygienic  

 Measuring principle 

An electrode inside the sensor tip builds a capacitor together with the sur-
roundings. The medium with its dielectric constant (DC value) is defining 
the capacitance value. A resonance circuit is created in combination with a 
coil in the sensor head. Switching signal tripping is according to the meas-
ured resonance frequency and the programmed trigger thresholds.  

Summary of Contents for CleverLevel LFFS-1 Series

Page 1: ...ption The Level Switch LFFS designed to detect levels in tanks media separation and provide empty pipe detection or dry run protection for pumps By means of the FlexProgrammer 9701 the output can be configured to either NPN PNP or digital output signal A damping of the output signal can be activated in case of a fluctuating media level e g during tank filling The measurement is precise and unaffec...

Page 2: ...Mounting instructions for sliding connection 1 Clean the sliding shaft 2 Mount the smallest ring against the media as indicated 3 Tighten the G1 2 Hygienic sliding nipple at 25 30 Nm 4 Replace the Washer ring kit when one or both parts are permanently deformed or stick to the shaft of the sliding connection The Level Switch LFFS with sliding connection can be mounted in installations with a static...

Page 3: ...ly Cannot be drained WARNING 5 The 3 A mark or the arrow shall be placed upwards 6 Welding should be grinded to Ra 0 8 7 Tighten the instrument in the adapter with a torque of 15 20 Nm If the seal is leaking and the media appears in the leak detection port the seal is to be changed immediately Before reassembly clean the hole and inside of the connection with detergent and sanitising liquid Use a ...

Page 4: ... DN 40 ZPH3 3254 for tank tube DN 50 ZPH3 3255 ZPW2 324 Adapter Welding EH FTL to pipe extrusion G A ZPH1 32BA DN 25 DN50 ZPW2 326 G1A ZPH1 32CB DN 65 DN150 ZPW2 327 VS G A ZPH1 32BC G1A ZPH1 32CD Adapter Adapter industrial Adapter industrial G G1 G G1 ZPI1 32B Sliding connection ZPH1 32C0 G G1 ZPI1 32D G G DIN 3852 E G G2 ZPI1 32E ZPI1 32A Welding for tank ZPW2 621 Welding for pipe end ZPW2 626 w...

Page 5: ...ank with a total in sertion length of 130 mm Hence the external length of the sliding connection will be 250 130 120 mm The media temperature will be max 160 C Read the x axis at 120 mm and the y axis at 160 C and find that the ambient temperature must be kept below 60 C In case the radiated heat from the tank will cause a higher ambient temperature at the housing efficient insulation of the tank ...

Page 6: ...ight on for 2 seconds Register full state stores the value and returns to Normal operation with new setting NOTE If the media is sticky foamy powdery or in other ways leaving parts of the media at the sensor tip this situation has to be estab lished also during the Teach In process Otherwise a faulty calibration can be the result If Teach In for some reason do not succeed the CleverLevel Switch LF...

Page 7: ...ed 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 www baumer com Operating instructions 11109132 09 EN Page 7 20 Active Low NPN and Digital output VDC 2 5V 0 5V Rload 1 kΩ Active High PNP and Digital output VDC 2 5V 0 5V Rload 1 kΩ ATEX Connection type Ambient temperature Media temperature max allowed Note G hygienic 40 85 C 85 C 3A DN38 40 60 C 95 C 1 40 40 C 115 C 1 100 mm 40 85 C 85 C Sliding connection 4...

Page 8: ... product must be installed in accordance with prevailing guidelines for zone 20 without a barrier Ex data Supply range VDC 12 5 30 Load I 0 1 A Temperature class T1 T5 Pls see table top page 7 12 5 30 1 2 5 ATEX Gas nA A Level Switch LFFS 3xx x is Ex nA II T5 ATEX II 3G approved for application in hazardous areas in accordance with the current EU directives The product must be installed in accorda...

Page 9: ...net sich hervorragend für die Füllstandserkennung in Behältern die Medientrennung sowie die Erkennung leerer Rohre und den Trockenlaufschutz von Pumpen Mithilfe des FlexProgrammer 9701 kann der Ausgang als NPN PNP oder ein digitales Ausgangssignal konfiguriert werden Im Falle eines veränderlichen Medienfüllstandes z B während der Befüllung des Behälters kann eine Dämpfung des Ausgangssig nals akti...

Page 10: ...werden Bitte keine Dichtungen aus PTFE Fasern oder sonstige Dich tungen verwenden Wenn sich die aus PEEK bestehende Spit ze gegen die Einschweissmuffe aus Edelstahl drückt bildet dies eine hygienegerechte Dichtung vorausgesetzt die Richtli nien wurden befolgt Aufgrund des Messprinzips ist es wichtig dass für die Sensor spitze ein ausreichend grosses Stück von Metallachse oder Einschweissmuffe sich...

Page 11: ...3A Markierung bzw der Pfeil sollte nach oben zeigen 6 Schweissnähte sollten so abgeschliffen werden dass sie einen Wert von Ra 0 8 aufweisen 7 Gerät im Adapter mit einem Drehmoment von 15 20 Nm festzie hen Wenn die Dichtung undicht ist und die Medien in der Kontrollbohrung sichtbar werden muss die Dichtung sofort ausgetauscht werden Vor dem erneuten Zusammenbau die Bohrung und das Innere des Ansch...

Page 12: ...254 für Behälter Rohr DN 50 ZPH3 3255 ZPW2 324 Adapter Einschweissmuffe EH FTL für Rohr mit Auszug G A ZPH1 32BA DN 25 DN50 ZPW2 326 G1A ZPH1 32CB DN 65 DN150 ZPW2 327 VS G A ZPH1 32BC G1A ZPH1 32CD Adapter Adapter Industriell Adapter Industriell G G1 G G1 ZPI1 32B verschiebbarer Anschl ZPH1 32C0 G G1 ZPI1 32D G G DIN 3852 E G G2 ZPI1 32E ZPI1 32A Einschweissmuffe für Behälter ZPW2 621 Einschweiss...

Page 13: ...von 130 mm in einen Tank montiert Seine externe Länge beträgt daher 250 130 120 mm Die Medientemperatur beträgt max 160 C Liest man den Schnittpunkt aus 120 mm auf der X Achse und 160 C auf der Y Achse ab so ergibt sich dass die Umgebungs temperatur unter 60 C gehalten werden muss Falls die Abstrahlwärme vom Behälter zu einer höheren Umgebungs temperatur am Gehäuse führt muss für eine wirksame Iso...

Page 14: ...rz an VDC anschliessen Leuchtet 2 Sekunden lang Registriert den Zustand gefüllt speichert den Wert und kehrt mit den neuen Einstellungen zum Normalbetrieb zurück ANMERKUNG Bei klebrigen schäumenden pulvrigen oder anderen Medien von denen leicht Reste an der Sensorspitze haften bleiben müssen diese Bedingungen auch während des Teach In Verfahrens vorliegen Andernfalls kann die Kalibrierung fehlerha...

Page 15: ... Schliesser NO Öffner NC Elektrische Daten Spannungsversorgung 12 5 36 VDC 35 mA max Ausgang PNP NPN oder Digital Max 50 mA kurzschlussfest und hochtemperaturfest Low aktiv NPN und digitaler Ausgang VDC 2 5V 0 5V Rload 1 kΩ High aktiv PNP und digitaler Ausgang VDC 2 5V 0 5V Rload 1 kΩ 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 1 2 5 www baumer com Betriebsanleitung 11109132 09 DE Page 15 20 PNP Ausgang NPN Aus...

Page 16: ...C 1 100 mm 40 85 C 85 C verschiebbarer Anschluss 40 60 C 155 C 1 40 40 C 175 C 1 250 mm 40 85 C 85 C verschiebbarer Anschluss 40 60 C 195 C 1 40 40 C 200 C 1 Bedingungen für Ex Zertifizierung 1 Gilt unter der Voraussetzung dass die Sensor spitze am Gerät als einziges Teil mit dem Medium in Berührung ist ATEX Gas ia LFFS 1xx x mit PNP Ausgang Safe area 22 120 VDC or 90 253 VAC ANMERKUNG Bei PNP Aus...

Page 17: ...Produkt ist gemäss den üblichen Richtli nien für Zone 2 ohne Barriere zu installieren Ex Daten Spannungsversorgung VDC 12 5 30 Last I 0 1 A Temperaturklasse T1 T5 Siehe Tabelle oben auf Seite 16 Der FlexProgrammer 9701 darf in der gefährlichen Umgebung nicht an den Füll standsschalter LFFS angeschlossen werden Vorgehensweise bei der Konfigurierung a Netz vom 4 20 mA Regelkreis trennen b Füllstands...

Page 18: ...WHG leakage and overfill protection approval Betriebsanleitung CleverLevel switch LFFS www baumer com Betriebsanleitung 11109132 09 DE Page 18 20 ...

Page 19: ...Betriebsanleitung CleverLevel switch LFFS www baumer com Betriebsanleitung 11109132 09 DE Page 19 20 WHG leakage and overfill protection approval ...

Page 20: ...www baumer com Betriebsanleitung 11109132 09 DE Page 20 20 For further information please refer to www baumer com ...

Reviews: