C2002 ELECTRONIC GOVERNOR
Date :
13-08-18
PowerKit Engine
Page :
9 / 15
Technoparc du Brégadan - 13260 Cassis / France
– Tel. +33 488 688 500
5.5
Speed droop operation
Droop is typically used for the paralleling of engine driven generators.
Place the optional external selector switch in the
DROOP
position, that is connected Terminals 10 and 11.
Droop is increased by clockwise rotation of the
DROOP
adjustment control. When in droop operation, the
engine speed will decrease as engine load increases. The percentage of droop is based on current change
from no load to full load of the actuator.
After the droop level has been adjusted, the rated engine speed setting may need to be reset. Check the
engine speed and adjust the speed setting accordingly.
5.6
Accessory input
When the Auxiliary Terminal 13 accepts input signals from load sharing units, auto synchronizers and
other governor system accessories are directly connected to this terminal. It is recommended that this
connection form accessories should be shielded as it is a sensitive input terminal.
When an accessory is connected to Terminal 13, the speed will decrease and the speed adjustment must
be reset.
5.7
Auxiliary power output
The +10 Volt regulated supply, Terminal 14, can be utilized to provide power to our governor system
accessories. Up to 20mA of current can be drawn from this supply. Ground reference is Terminal 7.
Caution : short circuit on this terminal can damage the speed Governor.