L62GB BASO Safety Shutoff Device Installation Instructions    

5

 

Technical Specifications 

Product 

L62GB BASO Safety Shutoff Device 

100% Shutoff 

Yes 

Conduit Opening 

2 (1 plugged) 

24/25 VAC 

125 VAC 

250 VAC 

Switch Contacts 

Electrical Specifications 

8 A 

4 A 

Ambient Temperature 

Range 

-40 to 175

°

F (-40 to 79

°

C) 

Reset 

Manual 

Switch Action 

SPST 

Type of Gas 

Natural, Liquefied Petroleum (LP), manufactured, mixed, or LP gas-air mixtures 

Rated Inlet Pressure 

0.5 psi (35 mbar) 

Packaging 

Bulk pack supplied to original equipment manufacturer (individual pack optional). L62GB-3 
supplied as individual pack only. 

Bulk Pack Quantity 

30 

Weight 

32 lb (14.5 kg) 

Agency Listings 

CSA Certificate Number 229521-1656085 

Specification Standards 

ANSI Standard Z21.20 
CAN1-6.4 

Switch can be used on 24/25 VAC installation. 

Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed 
under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void 
the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original 
equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for 
questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or 
misuse of its products. 

Refer to the 

L61, L62 Series BASO Safety Shutoff Device Product Bulletin (BASO-PB-L61/L62)

 for necessary information on operating and 

performance specifications of this product. 

1007 South 12th Street 
PO Box 170 
Watertown, WI  53094 

www.baso.com

1-877-227-6427 (1-877-BASOGAS) 

Published in U.S.A.

Summary of Contents for L62GB

Page 1: ...and cause the safety switch to fail 4 Mount the L62GB in any convenient position using the mounting holes in the back of the case 5 Push the circuit wires through the conduit opening on the side of the device strip the ends of the wires just enough to put the bare wire under the terminal screws and attach them to the two wire terminals WARNING Risk of Explosion or Fire Do not attach both wires to ...

Page 2: ...or fire and may result in severe personal injury or death Make sure all components are functioning properly by performing the following test 1 Test all joints and connections for leaks with a soap solution 2 Set the thermostat to the lowest setting 3 Close the main manual shutoff valve A valve and the pilot valve B valve see Figure 1 and wait at least 5 minutes for unburned gas to escape from the ...

Page 3: ...ge mA Range of Power Unit Assembly Low High 100 300 Pilot Servicing If pilot flame problems occur check the following If the pilot flame burns yellow it may be due to dirt or lint covering the lower portion of the pilot burner Remove dirt and lint using a soft brush or a vacuum cleaner A flame approximately 0 5 in 12 7 mm high must surround the thermocouple tip see Figure 2 Because this is an elec...

Page 4: ...e with the sheet metal screws provided The mounting plate is not required for exact replacements 1 2 4 5 3 Universal Mounting Plate BASO Power Unit Terminal Wire Terminals L62GB 3 Cover Figure 3 L62GB 3 Mounting 8 Mount the L62GB 3 using the holes in the universal mounting plate that match the mounting holes for the device being replaced see Table 3 Table 3 Mounting Guide Switch Being Replaced Use...

Page 5: ... Performance specifications are nominal and conform to acceptable industry standards All agency certification of BASO products is performed under dry and controlled indoor environmental conditions Use of BASO products beyond these conditions is not recommended and may void the warranty Product must be protected if exposed to water dripping spraying rain etc or other harsh environments The original...

Reviews: