Baso L62GB Installation Instructions Download Page 1

 

 

   

 

Installation Instructions   

 

Issue Date  March 5, 2013 

 

©  2013 BASO Gas Products.

 

1

 

  Part No. BASO-INS-L62GB, Rev. B 

www.baso.com 

L62GB BASO® Safety Shutoff Device 

Installation 

IMPORTANT: 

Only qualified personnel should 

install or service BASO® Gas Products. These 
instructions are a guide for such personnel. Carefully 
follow all instructions in this document and all 
instructions for the appliance. 

 

!

  WARNING: Risk of Explosion or Fire. 

Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the L62GB. 
Failure to shut of the gas supply can result in the 
release of gas during installation or servicing, which 
can lead to an explosion or fire, and may result in 
severe personal injury or death. 

 

!

  CAUTION:  Risk of Electric Shock. 

Disconnect power supply before making electrical 
connections to avoid electric shock. 

 

IMPORTANT: 

Make all gas installations in 

accordance with applicable local, national, and 
regional regulations. 

To install the L62GB. 

1.  Turn off power to the appliance. 

2.  Turn off gas at the main manual shutoff valve 

adjacent to the appliance. 

3.  Remove the L62GB cover by loosening the screw 

on the front of the device. 

IMPORTANT: 

Do not loosen or tighten the 

brass hex nut that fastens the brass terminal 
bushing to the plastic switch housing. The machined 
flats on the terminal bushing must be parallel to the 
flats on the switch housing. If not, the switch power 
unit may distort and cause the safety switch to fail. 

4.  Mount the L62GB in any convenient position using 

the mounting holes in the back of the case. 

5.  Push the circuit wires through the conduit opening 

on the side of the device, strip the ends of the 
wires just enough to put the bare wire under the 
terminal screws, and attach them to the two wire 
terminals. 

!

  WARNING: Risk of Explosion or Fire. 

Do not attach both wires to one terminal on the 
L62GB. Doing so bypasses and eliminates all safety 
features provided by the L62GB, can lead to an 
explosion or fire, and may result in severe personal 
injury or death. 

 

!

  WARNING: Risk of Explosion or Fire. 

Verify that this device is wired in series electrically 
with thermostats and other appliance operating 
controls. Wiring the device in parallel with such 
controls will defeat the safety features of this device 
and may result in severe personal injury or death. 

6.  Replace the cover. 

Do not loosen or tighten the 

brass hex nut.

 

7.  Connect the pilot burner orifice fitting to the pilot 

outlet on the L62GB with 1/4 in. outside diameter 
tubing, and connect the pilot gas inlet with the gas 
manifold upstream from the automatic valve. 

Note: 

The pilot line connection is bidirectional as 

indicated by the arrows pointing in either direction. 
This provides the option of connecting the pilot gas 
inlet and outlet in either position. 

8.  Attach the thermocouple securely to the pilot 

burner, and screw the terminal end to the BASO® 
power unit terminal on the L62GB. Make sure that 
this connection is clean. Tighten the thermocouple 
lead nut finger tight plus a maximum of 1/8 turn. 

Do not overtighten

Summary of Contents for L62GB

Page 1: ...and cause the safety switch to fail 4 Mount the L62GB in any convenient position using the mounting holes in the back of the case 5 Push the circuit wires through the conduit opening on the side of the device strip the ends of the wires just enough to put the bare wire under the terminal screws and attach them to the two wire terminals WARNING Risk of Explosion or Fire Do not attach both wires to ...

Page 2: ...or fire and may result in severe personal injury or death Make sure all components are functioning properly by performing the following test 1 Test all joints and connections for leaks with a soap solution 2 Set the thermostat to the lowest setting 3 Close the main manual shutoff valve A valve and the pilot valve B valve see Figure 1 and wait at least 5 minutes for unburned gas to escape from the ...

Page 3: ...ge mA Range of Power Unit Assembly Low High 100 300 Pilot Servicing If pilot flame problems occur check the following If the pilot flame burns yellow it may be due to dirt or lint covering the lower portion of the pilot burner Remove dirt and lint using a soft brush or a vacuum cleaner A flame approximately 0 5 in 12 7 mm high must surround the thermocouple tip see Figure 2 Because this is an elec...

Page 4: ...e with the sheet metal screws provided The mounting plate is not required for exact replacements 1 2 4 5 3 Universal Mounting Plate BASO Power Unit Terminal Wire Terminals L62GB 3 Cover Figure 3 L62GB 3 Mounting 8 Mount the L62GB 3 using the holes in the universal mounting plate that match the mounting holes for the device being replaced see Table 3 Table 3 Mounting Guide Switch Being Replaced Use...

Page 5: ... Performance specifications are nominal and conform to acceptable industry standards All agency certification of BASO products is performed under dry and controlled indoor environmental conditions Use of BASO products beyond these conditions is not recommended and may void the warranty Product must be protected if exposed to water dripping spraying rain etc or other harsh environments The original...