Basler DECS-200 Instruction Manual Download Page 5

DECS-200 Digital Excitation Control System

5

Off-Line

High Current Level

 (instantaneous) set point adjustable from 0 to 30Adc in 0.1Adc increments.

Limiting occurs for a time period ranging from 0 to 10 seconds, settable in 1 second increments.

Low Current Level

 set point adjustable from 0 to 15Adc in 0.1Adc increments. Limiting occurs in-

definitely.

TAKEOVER TYPE OEL:  

The Takeover OEL uses an I

2

t characteristic.

On-Line

High Level: 

High Current Level

 

(instantaneous) set point is adjustable from 0 to 30.0Adc in 0.1

Adc increments.

Low Level: 

Low Current set point is adjustable from 0 to 15.0Adc in 0.1Adc increments. Limint

occurs indefinitely.

Time Dial

 - This setting determines the inverse time curve selected.

Off-Line

High Level - 

High current level (instantaneous) set point is adjustable from 0 to 30.0Adc in

0.1Adc increments.

Low Level

 - Low current set point is adjustable from 0 to 15.0Adc in 0.1Adc increments. Limiting

occurs indefinitely.

Time Dial

 - This setting determines the inverse time curve selected.

UNDEREXCITATION LIMITING

 Adjustments based on generator ratings.

STATOR CURRENT LIMITING

High Level

 - High current level set point adjustable from 0 to 60,000Aac in 0.1Aac increments.

Limiting occurs for a time period ranging from 0 to 60 seconds, settable in 0.1 sec. increments.

Low Level

 - Low current level set point adjustable from 0 to 60,000Aac in 0.1Aac increments.

Limiting occurs indefinitely.

SEQUENCE OF EVENT RECORDING (SER)  

127 event reports stored in volatile memory (retrievable via

BESTCOMS). SER triggered by: Input/Output status changes, system operating status changes, and alarm annun-
ciations.

OSCILLOGRAPHY

  Stores 8 records. Up to 6 variables can be logged in a record. Sampling rate: 600 data points

per log, pre-trigger adjustable from 0 to 599 data points, 4ms to 10sec intervals between data points (2.4sec to
6000sec. total log duration)

MANUAL EXCITATION CONTROL

  Regulates field current from 0 to 15.0A in increments of 0.1Adc.

VOLTAGE MATCHING

  Matches utility bus RMS voltage with generator output RMS voltage within ±0.15% of

the generator voltage

REAL TIME CLOCK

  Time displayed in either 12 hour or 24 hour format and can be selected to allow for daylight

savings timer. The date is selectable for two formats: d-m-y or m/d/y. Requires control power to operate. If power is
lost, the clock will need to be reset.

SURGE WITHSTAND CAPABILITY (SWC)  

IEEE C37.90.1-1989

FAST TRANSIENT  

IEEE C37.90.1-1989

HIGH POT. 

IEEE 421.3

ENVIRONMENTAL
Operating temperature

: -40°C to +60°C (-40°F to +140°F)  

Storage temperature:

 -40°C to +85°C (-40°F to +185°F)

Salt Fog

  Per MIL-STD-810E, Method 509.3 (100 hrs. of salt fog, 100 hours of drying time)

Shock

  15 Gs in each of three mutually perpendicular planes

Vibration

  5-26Hz: 1.2Gs;  27-52Hz: 0.914mm (.036 inch) double amplitude; 53-500Hz: 5.0Gs

Size  

8.08" (205mm) wide x 6.76" (171mm) deep x 12.0" (304mm) high

Weight

  14 lbs. (6.35kg)

AGENCY

  UL recognized per Std. 508; UL file number E97035; CSA certified per Std. CAN/CSA-C22.2,

Number 14, CSA file number LR23131; CE compliant, EMC and LVD; Certified per DNV Standard 2.4; GOST-R
certified per the relevant standards of Gosstandart of Russia; Byelorussian certified.

SPECIFICATIONS, continued

Summary of Contents for DECS-200

Page 1: ...TION INSTRUCTION MANUAL Request Publication 9360100990 WINDOWS SOFTWARE Interface for setting and communicating with Basler products Request DECS 200 CD Microprocessor based design True RMS sensing si...

Page 2: ...ins all the functionality necessary to limit control and protect a generator from operating outside of the machine s capability A feature of DECS 200 s sophisticated design allows the nonactive contro...

Page 3: ...7 0 120 240 Vac 7 0 COMMUNICATION There are three communication ports two RS 232 and one RS 485 COM0 RS 232 9 pin sub D connector located on front panel and used to communicate with local computers 1...

Page 4: ...ss generators To do this the DECS 200 requires the user to input the number of generator poles and the number of exciter poles both adjustable from 0 to 20 in increments of 2 The open and shorted diod...

Page 5: ...memory retrievable via BESTCOMS SER triggered by Input Output status changes system operating status changes and alarm annun ciations OSCILLOGRAPHY Stores 8 records Up to 6 variables can be logged in...

Page 6: ...justs the operating mode across its predetermined adjustment range The auxiliary input can be provided from other controlling devices such as a power system stabilizer These devices modify the operati...

Page 7: ...sing Field Overvoltage Loss of field Field Overcurrent EDM Exciter Diode Monitor Sequence of Events Recording SER A sequence of event report SER is a very powerful tool when reconstructing the exact t...

Page 8: ...DECS 200 Digital Excitation Control System 8 CONNECTIONS Figure 1 Typical AC Connection Diagram...

Page 9: ...lling Pushbuttons Scrolls UP DOWN LEFT RIGHT through the menu tree or when in the EDIT mode the LEFT RIGHT scrolling pushbuttons select the variable to change and the UP DOWN scrolling pushbuttons cha...

Page 10: ...DECS 200 Digital Excitation Control System Figure 3 Dimensions DIMENSIONS Front view Top view 10...

Page 11: ...rrent Reduction Module is required when energizing the DECS 200 from a source that is already at the regulator s input power ratings This module minimizes the amount of inrush current that could be se...

Page 12: ...1 618 654 2341 Fax 1 618 654 2351 e mail info basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R China Tel 86 0 512 8227 2888 Fax 86 0 512 8227 2887 e mail china...

Reviews: