Basler DECS-200 Instruction Manual Download Page 2

DECS-200 Digital Excitation Control System

2

FEATURES, continued

DESCRIPTION

INPUTS
Control Power (style selectable)

16-60Vdc, Burden=30W.

 

85-132Vac, 50 or 60Hz, Burden=50VA. 90-150Vdc, Burden=30W.

AC Operating Power

1 or 3 Phase Power Input

DECS-200 Output

AC Voltage Nominal

    Range (50-500Hz)

Burden

32Vdc

60Vac

56-70Vac ±10%

780VA

63Vdc

120Vac

100-139Vac ±10%

1570VA

125Vdc

240Vac

190-277Vac ±10%

3070VA

NOTES:
1)For applications that require the DECS-200 from a source that is already at the regulator's rated power input voltage level, an Inrush

Current Reduction Module is needed to minimize the amount of inrush current that may occur. Refer to Accessories (see page 11),
regarding ICRM-15.

2)To achieve the proper DECS-200 output voltage, the associated Operating Power must be provided. Min. voltage buildup: 3 Vac.

Generator Voltage Sensing

Single-phase or three-phase line voltage, four ranges:
• 100V/50Hz nominal (85 to 127V), 120V/60Hz nominal (94 to 153V)
• 200V/50Hz nominal (170 to 254V), 240V/60Hz nominal (187 to 305V)
• 400V/50Hz nominal (340 to 508V), 480V/60Hz nominal (374 to 600V)
• 500V/50Hz nominal (425 to 625V), 600V/60Hz nominal (510 to 660V)

Bus Voltage Sensing

Single-phase line voltage (AC), four ranges:
• 100V/50Hz nominal (85 to 127V), 120V/60Hz nominal (94 to 153V)
• 200V/50Hz nominal (170 to 254V), 240V/60Hz nominal (187 to 305V)
• 400V/50Hz nominal (340 to 508V), 480V/60Hz nominal (374 to 600V)
• 500V/50Hz nominal (425 to 625V), 600V/60Hz nominal (510 to 660V)

SPECIFICATIONS

The microprocessor based DECS-200 is a total excita-
tion control system in one enclosure. It contains all the
functionality necessary to limit, control, and protect a
generator from operating outside of the machine's
capability. A feature of DECS-200's sophisticated
design allows the nonactive control mode within the
unit to follow the active mode, permitting bumpless
transfer between modes. The optional external tracking
feature also allows for unit-to-unit communication,

permitting autofollowing and transfer between DECS-
200 units. It can also communicate to a PC via the front
panel RS-232 port for local programming and metering,
and it can communicate via Modbus™ protocol via the
side RS-485 port for communications up to 4000 feet
away from the DECS-200 unit. The DECS-200 has all
the features, functionality, flexibility and programmabil-
ity expected from a state-of-the-art microprocessor
based product.

• Voltage Matching
• Eight (8) generator protection features
• Programmable output contacts
• Front panel backlit LCD display
• Front panel mounted RS-232 and side RS-485

communications ports

• Modbus™ protocol for RS-485 input allows

communications up to 4000 feet away

• <1% metering accuracy for 12 generator parameters

• Remote set point control via:

- Contact inputs
- Proportional control via ±10Vdc or 4-20mA
- Communications inputs RS-232 (ASCII) or RS-485
  (Modbus™)

• Meets C37.90.1-1989 for Surge Withstand and Fast

Transient

• UL recognized, CSA certified, CE compliant, DNV

certified, GOST-R certified, Byelorussian certified

• U.S. Patent Number 5,294,879

APPLICATIONS

The DECS-200 is an excitation control system used to control the output voltage, vars or power factor of a
synchronous generator by varying or controlling the amount of dc excitation applied to the generator's exciter
field. The DECS-200 is suitable for virtually any size machine.

Summary of Contents for DECS-200

Page 1: ...TION INSTRUCTION MANUAL Request Publication 9360100990 WINDOWS SOFTWARE Interface for setting and communicating with Basler products Request DECS 200 CD Microprocessor based design True RMS sensing si...

Page 2: ...ins all the functionality necessary to limit control and protect a generator from operating outside of the machine s capability A feature of DECS 200 s sophisticated design allows the nonactive contro...

Page 3: ...7 0 120 240 Vac 7 0 COMMUNICATION There are three communication ports two RS 232 and one RS 485 COM0 RS 232 9 pin sub D connector located on front panel and used to communicate with local computers 1...

Page 4: ...ss generators To do this the DECS 200 requires the user to input the number of generator poles and the number of exciter poles both adjustable from 0 to 20 in increments of 2 The open and shorted diod...

Page 5: ...memory retrievable via BESTCOMS SER triggered by Input Output status changes system operating status changes and alarm annun ciations OSCILLOGRAPHY Stores 8 records Up to 6 variables can be logged in...

Page 6: ...justs the operating mode across its predetermined adjustment range The auxiliary input can be provided from other controlling devices such as a power system stabilizer These devices modify the operati...

Page 7: ...sing Field Overvoltage Loss of field Field Overcurrent EDM Exciter Diode Monitor Sequence of Events Recording SER A sequence of event report SER is a very powerful tool when reconstructing the exact t...

Page 8: ...DECS 200 Digital Excitation Control System 8 CONNECTIONS Figure 1 Typical AC Connection Diagram...

Page 9: ...lling Pushbuttons Scrolls UP DOWN LEFT RIGHT through the menu tree or when in the EDIT mode the LEFT RIGHT scrolling pushbuttons select the variable to change and the UP DOWN scrolling pushbuttons cha...

Page 10: ...DECS 200 Digital Excitation Control System Figure 3 Dimensions DIMENSIONS Front view Top view 10...

Page 11: ...rrent Reduction Module is required when energizing the DECS 200 from a source that is already at the regulator s input power ratings This module minimizes the amount of inrush current that could be se...

Page 12: ...1 618 654 2341 Fax 1 618 654 2351 e mail info basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R China Tel 86 0 512 8227 2888 Fax 86 0 512 8227 2887 e mail china...

Reviews: