BE1-MMS100
FUNCTIONAL DESCRIPTION,
continued
INDICATORS
Power indicator is the green LED on the left hand side
of the indicator group. This is used to indicate operat
ing power applied; the power supply is operational
and within specifications.
Unit Status is a red LED next to the green Power LED.
This LED flashes once per second when unit is work
ing properly.
Rx is a red LED. This LED flashes when the rear port
Rx (receive) signal line is high.
Tx is a red LED. This LED flashes when the rear port Tx
(transmit) signal line is high.
Freeze Display indicator is on the right hand side of
the indicator group and is used to indicate that the
LCD is "frozen", or locked on present display.
The LED in the EDIT key illuminates when the unit is in
program setup mode.
KEYPAD USAGE
There are six pushbuttons: Up arrow, Down arrow, Left
arrow, Right arrow, EDIT, and RESET.
The RESET pushbutton is used to set the time interval
for 15 minute averages, the elapsed time indicator,
and the imported, exported, and accumulated kWh,
kVARh and kVAh. The reset function has a prompt to
avoid accidental operation.
The EDIT pushbutton is used to set the unit in set up
mode. In set up mode the protocol, the delta or wye
configuration, the port baud rate, the address, and call
home phone number are selected. If password protec
tion is used, the proper password must be entered to
operate the EDIT pushbutton.
The arrow pushbuttons are used to set and change
the numeric parameters.
Multifunction Meter System
Style Number:
XXXXXX
Sensing Input Range:
XX XX, XX X
Power Supply: 48/125V
AC/DC
Serial Number:
XXXXXXXXXX
Unit
Freeze
Power Status
Rx
Tx
Display
0
0
0
0
0
BE1-MMS
COM�
RS-232
Figure 1 - Front p anel of BE1-MMS1 00
LCD DISPLAY USAGE
The LCD display is a 16 character by two-line display.
When the unit is first powered up, the LCD displays
"Executing Application", then switches to the "top
level" display, which shows the Model Number and
software version.
If no keys are pressed, the LCD switches to metering
mode and alternately displays the various parameters
measured. This is called scrolling. When the down
arrow key is pressed, "Freeze Display" LED lights up
and the display locks on the last screen. Press
again and the display resumes scrolling, or it will
automatically resume scrolling after five minutes.
The Metering screens include:
Screen
Parameter
Metering "a"
kWh
kVARh
Metering "b"
Wh Imported
Metering "c"
Wh Exported
Metering "d"
VARh Imported
Metering "e"
VARh Exported
Metering
"
f
"
VAh Imported
Metering "g"
VAh Exported
Metering "h"
VAh Accumulated
Metering "i"
kW
kVAR
Metering "j"
Volts A
Volts B
Volts C
Metering "k"
Amps A
Amps B
Amps C
Metering "I"
Amps N
Metering "m"
Frequency
PF
Metering "n"
THD A
THO B
THD C
Metering "o"
Time
Date
Metering "p"
Accumulated Time
10
10
10
10
10
10
10
10
10
10
10
6
6
6
6
6
6
6
3
3
6
6
6
8
10
10
There are three data acquisition and control protocol
formats available through the front panel or via the
communication ports. These formats are transducer
network protocol (TNP, includes oldET), ModbusTM,
and distributed network protocol DNP. The user
makes this choice using the HMI setup procedures.
The communication ports support an 8, N
,
1 byte format
and connect at the following baud rates: 300, 600,
1200, 2400, 4800, 9600, and 19200.