BE1-851E

FUNCTIONAL DESCRIPTION

The BE1-851E is a multifunction, numeric relay that
provides a comprehensive mix of protective, control
and metering functions in an integrated system. This
system is suitable for any nondirectional overcurrent
application including feeder applications, generator
applications, cogeneration applications, and trans-
former backup.

The BE1-851E has the unique ability to provide specific
current response characteristics. It does this in three
different ways:
• The Fundamental twenty-four sample per cycle

Digital Signal Processing (DSP) algorithm provides
rejection of harmonics and low transient overreach.

• The RMS DSP algorithm provides true wide band

RMS measurement.

• The Average DSP algorithm provides a flat

response characteristic over a wide frequency
range.

These characteristics are independently settable for
phase and neutral quantities.

The unit has one set of three phase and neutral current
sensing inputs to provide all common protective
functions for substation and feeder applications.

The half rack case is fully drawout with current circuit
shorting provisions. Two Basler Electric half rack IEDs
(Intelligent Electronic Devices) such as primary and
backup BE1-851E or the BE1-951 or BE1-GPS100 can
be dovetailed together to mount in a standard 19"
equipment rack with no special mounting hardware.

Three independent communications ports, along with
built-in support for Modbus

™ 

and other common

protocols, provide easy access to integrating the
protection, control, metering, and status monitoring
functions into a substation automation system. The
standard IRIG-B port provides time synchronization
from a master clock.

Real time metering provides amp and unbalance
loading telemetry for the protected circuit. Contact
sensing inputs and alarm monitoring functions provide
real time status information. Remote control is provided
by virtual control and selector switches with select-
before-operate control of programmable outputs.

BESTlogic

BESTlogic programmable logic provides the user with
high flexibility in configuring a protection and control
system.

Each of the protection and control functions in the
BE1-851E is implemented as an independent function
block that is equivalent to its single function, discrete
device counterpart. Each independent function block
has all the inputs and outputs that the discrete
component counterpart might have. Figure 6 shows
each of the independent function blocks available for
use in the BE1-851E. Programming BESTlogic is
equivalent to choosing the devices required by your
protection and control scheme and drawing schematic
diagrams to connect the inputs and outputs to obtain
the desired operational logic.

The BE1-851E relay can store, as user settings, one
user programmable, custom logic scheme. To save
you time, several preprogrammed logic schemes have
also been provided. Any of the preprogrammed
schemes may be copied into the logic settings without
making any additional BESTlogic settings.

BESTlogic provides the protection engineer with the
flexibility to set up this powerful multifunction system
with the same freedom that was once enjoyed with
single function, discrete devices. It is no longer neces-
sary to compromise your standard protection and
operating practices to deal with the limitations in
programmability of previous multifunction devices.

Figures 2A, 2B, 2C, and 3 show typical external
connections, and Figure 5 shows rear panel connec-
tions.

4

Summary of Contents for BE1-851E

Page 1: ...he relay to replace local indication and control functions such as panel metering alarm annunciation and control switches Three independent communication ports with protocol support allows integration with distributed control systems Real Time Clock with 8 hour capacitor ride through and optional battery backup Available in a fully drawout case configuration FEATURES Pages 2 and 3 APPLICATIONS Pag...

Page 2: ...fault report Fault summary reports two most recent Fault Summary Records saved to non volatile memory 16 fault records 15 cycles long 24 samples cycle COMTRADEformat COMMUNICATIONPORTS Threeindependentgeneralpurposecommunica tion ports Front RS 232 ASCII communications Rear RS 232 ASCII communications Rear RS 485 ASCII Modbus DNP or other common protocols IRIG B time sync unmodulated SELF TEST AND...

Page 3: ...nd remote indication metering and control functions required on a typical circuit Applications that require communication capability Applications that require specific current response characteristics The fundamental digital signal processing DSP algorithm provides rejection of harmonics and low transient overreach The RMS DSP algorithm provides true wide band RMS measurement The average DSP algor...

Page 4: ...chronization from a master clock Real time metering provides amp and unbalance loading telemetry for the protected circuit Contact sensing inputs and alarm monitoring functions provide real time status information Remote control is provided by virtual control and selector switches with select before operate control of programmable outputs BESTlogic BESTlogic programmable logic provides the user wi...

Page 5: ...2A Typical External Sensing Connections Feeder Breaker Application Figure 2B Typical External Sensing Connections Transformer Backup Application FUNCTIONAL DESCRIPTION continued 5 Figure 2C Alternate Connections for IN ...

Page 6: ...BE1 851E Figure 3 Typical External Connections FUNCTIONAL DESCRIPTION continued 6 Figure 4 Typical Application Single Line ...

Page 7: ...BE1 851E FUNCTIONAL DESCRIPTION continued Figure 5 BE1 851E Rear Panel Connections 7 ...

Page 8: ...BE1 851E Figure 6 BESTlogic Function Blocks 8 ...

Page 9: ...rdSurgeWithstand Capability Tests for Relays and Relay Systems Associated with Electric Power Apparatus IEC 255 22 1 1MHz Burst Disturbance Tests for Electrical Disturbance Tests for Measuring Relays and Protection Equipment EN 61000 4 4 Electrical Fast Transient Burst Immu nity Test EN 61000 4 3 Radiated Radio frequency Electro magnetic Field Immunity Test Type tested using a 5 watt hand held tra...

Page 10: ...75mA SETTING GROUPS Setting Groups 4 Control Modes Automatic CLP Dynamic load or unbalance External Discrete input logic Binary Input Logic METERING Current Range 5A 0 5 to 15 0 1A 0 1 to 3 0 Current Accuracy 1 DEMANDS IA IB IC IN IQ Demand Interval 1 60 min Demand Mode Thermal BREAKER MONITORING Duty Mode I or I2 Duty Alarm Range 0 100 Op Counter Alarm Range 0 99999 Trip Time Alarm Range 20 1000 ...

Page 11: ... Supply K H1 type case with normally open alarm output contacts 0 ASCII protocol communication via RS 485 U Battery backup for Real Time Clock 00 None 9289900017 Escutcheon plate to panel mount one H1 relay 9289900016 Escutcheon plate to panel mount two dovetailed H1 relays 9289924100 Adapter bracket to mount single H1 case in 19 rack 9289929100 Adapter bracket with cutout for ABB FT test switch t...

Page 12: ...el 1 618 654 2341 Fax 1 618 654 2351 e mail info basler com www basler com P A E Les Pins 67319 Wasselonne Cedex FRANCE Tel 33 3 88 87 1010 Fax 33 3 88 87 0808 e mail beifrance basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R China Tel 86 0 512 6346 1730 Fax 86 0 512 8227 2888 e mail beichina basler com ...

Reviews: