9310200990 Rev G
BE1-79A Communication Commands
4-3
For clarity in the examples, relay responses are printed in the
Courier
typeface.
EXIT command example: exit after making setting changes.
EXIT
>SAVE CHANGES (Y/N/C)?
Prompt to save (Y)es, discard changes (N)o, or (C)ontinue
>Y
Confirmation to save changes
CHANGES SAVED
Confirmation that changes were saved
Obtaining Help Information Through the Serial Port
The HELP or H command provides general help information on command syntax and functionality when
the manual is not available. Help is available only when the relay is in a reset state.
HELP
Command
Purpose
:
Obtains help on using serial port commands.
Syntax
:
HELP or H
Comments
:
The HELP command returns a listing of all available commands along with the proper
syntax for each command.
Obtaining a Summary of All Settings
All relay settings may be listed using the S command.
S
Command
Purpose
:
Read all relay settings back to user.
Syntax
: SP-79A[n]
Comments
: S by itself may be used to read all relay settings. SP-79A[n] is used to read a specific
setting. the S command can be used to make a record of the relay settings after they have
been set.
S command example: Obtain a report of the relay settings.
A=
S
SP-79A1 5,10
SP-79A2 15,20
SP-79A3 25,30
SP-79A4 35,40
SP-79ALO 45,50
SP-79ARS D,0,5
SP-ALM 2
>
Reclose and Reset Timer Setting Command
SP-79A
Command
Purpose
:
Read or change the reclose and reset timer settings.
Syntax
:
S[-79a[n][=<reclose time delay>,<reset time delay>]
Comments
:
n: reclose number of LO for lockout. See Table 4-1 for setting defaults.
reclose time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A Reclose 1
setting of zero will cause an instantaneous first reclosure. A setting of zero for any other
reclose time delay will disable the reclose shot.
reset time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A reset time delay
setting of zero will cause the reset to be disabled. A reset time delay setting less than the
reclose time setting will cause an immediate reset following the reclose attempt.
SP-79A command example: Read the second reclose and reset timer settings.
A=
SP-79A2
15.0,20.0
>
Summary of Contents for BE1-79A
Page 1: ...INSTRUCTION MANUAL FOR RECLOSING RELAY BE1 79A Publication 9310200990 Revision G 02 08...
Page 2: ......
Page 8: ...vi BE1 79A Introduction 9310200990 Rev G This page intentionally left blank...
Page 10: ...ii BE1 79A General Information 9310200990 Rev G This page intentionally left blank...
Page 16: ...ii BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 20: ...2 4 BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Page 22: ...ii BE1 79A Functional Description 9310200990 Rev G This page intentionally left blank...
Page 34: ...ii BE1 79A Communication Commands 9310200990 Rev G This page intentionally left blank...
Page 40: ...ii BE1 79A Installation and Configuration 9310200990 Rev G This page intentionally left blank...
Page 52: ...ii BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 58: ...6 6 BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Page 60: ...ii BE1 79A RS Contact Application 9310200990 Rev G This page intentionally left blank...
Page 66: ...ii BE1 79A Terminal Communication 9310200990 Rev G This page intentionally left blank...