9252000894 Rev D
BE1-50/51B-230/-234 General Information
1-3
Instantaneous Overcurrent B (50-B) Element
BE1-50/51B-230 Pickup
Setting Range:
1 to 15.9 Aac
Setting increment:
0.1 Aac
Accuracy: Sum
of
±
2% and
±
25 mAac
BE1-50/51B-234 Pickup
Setting Range:
0.2 to 3.18 Aac
Setting increment:
0.02 Aac
Accuracy: Sum
of
±
2% and
±
5 mAac
Dropout
Dropout occurs at 95% of pickup value.
Time Delay
Fixed at no intentional delay. Appendix A,
Characteristic Curves
illustrates the characteristic curve for the
50-A and 50-B elements.
Reset Characteristic
Resets within 16 ms of when sensed current decreases below the pickup level.
Current Sensing Input
BE1-50/51B-230
Continuous Rating:
14 Aac
∗
1 Second Rating:
400 Aac
∗
Continuous rating is 14 Aac for temperatures up to 45
°
C. See Figure 1-1 for derating curve.
Continuous Current
Current Sensing Input
0
2
4
6
8
10
12
14
16
-40
-20
0
20
40
60
Ambient Temperature (C)
C
u
rr
ent (A
ac)
Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-230)
Summary of Contents for BE1-50B-230
Page 2: ......
Page 6: ...iv BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 8: ...vi BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 10: ...ii BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 18: ...1 8 BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 32: ...ii BE1 50 51B 230 234 Installation 9252000894 Rev D This page intentionally left blank...
Page 38: ...ii BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...
Page 50: ...5 12 BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...