BE1-49 General Information
SPECIFICATIONS
Sensing Method
Four wire, using a remotely installed 10 ohm copper or
100 ohm platinum resistive temperature detector (RTD)
located within the protected machine. Relay supplies
constant 40 mA current and senses voltage across the
temperature sensitive resistance element.
Outputs
Resistive
Inductive
Output contacts are rated as follows.
120/240 Vac - make 30 A for 0.2 seconds, carry 7 A
continuously, break 7 A. 250 Vdc - make and carry 30 A
for 0.2 seconds, carry 7 A continuously, break 0.1 A. 500
Vdc - make and carry 15 A for 0.2 seconds, carry 7 A
continuously, break 0.1 A.
120/240 Vac, 125 Vdc, 250 Vdc - break 0.1 A (L/R = 0.04).
Power Supply
One of the six types of power supplies listed in Table 1-2
may be selected to provide internal relay operating power.
Table 1-2. Power Supply Types And Specifications
Type
Nominal Input
Voltage
Input Voltage
Range
Burden at
Nominal
B (Mid Range)
48 Vdc
24 to 150 Vdc
4.0 W
C (Mid Range)
125 Vdc
120 Vac
24 to 150 Vdc
90 to 132 Vac
4.5 W
10.3 VA
D (Low Range)
24 Vdc
12 to 32 Vdc
t
4.0 W
E (Mid Range)
125 Vdc
120 Vac
24 to 150 Vdc †
90 to 132 Vac
4.5 W
10.3 VA
W (Mid Range)
48 Vdc
125 Vdc
24 to 150 Vdc
24 to 150 Vdc
4.0 W
4.5 W
X (High Range)
250 Vdc
240 Vac
62 to 280 Vdc
90 to 270 Vac
5.2 W
14.0 VA
t
Type D power supply initially requires 14 Vdc to begin operating. Once operating,
the voltage may be reduced to 12 Vdc and operation will continue.
† Prior to 1996, Type E power supply accepted only ac input power. See the power
supply discussion in Section 3,
Functional Description
.
Target Indicator
A magnetically latched, manually reset, target indicator is
optionally available to indicate that the output has tripped.
An internally operated or current operated target may be
specified. A current operated target requires 0.2 A in the
output trip circuit to actuate, and trip circuit current must
not exceed 30 A for 0.2 seconds, 7 A for 2 minutes, and 3
A continuous. A current operated target may be selected
only when normally open (NO) output contacts have been
specified.
Summary of Contents for BE1-49
Page 2: ......
Page 6: ...This page intentionally left blank...
Page 12: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 27: ...BE1 49 Installation 4 9 Figure 4 8 S1 Case Panel Drilling Diagram Semi Flush Mounting...
Page 30: ...4 12 BE1 49 Installation Figure 4 11 DC Connection Diagram...
Page 38: ...This page intentionally left blank...
Page 40: ...This page intentionally left blank...
Page 41: ......