Basler BE1-32 Quick Start Manual Download Page 5

BE1-32R, BE1-32R O/U

5

SPECIFICATIONS

(continued)

If sensing input range 2, 3, 5, 6, 8 or 9 is selected, the

input transformers are capable of 10 A continuous

current, 15 A for 1 minute and 200 A for 1 second.

Maximum burden for each current input (2 terminals) is

1 VA at threshold over the frequency range of 45 to

65 Hz.

Voltage Sensing

System potential transformers (PTs) with 120 or 240V

secondaries supply the Directional Power Relay’s input

transformers with single or three-phase voltages. The

voltage sensing inputs are nominally rated at 100 or

220V (50 Hz) and 120 or 240V (60 Hz) with a maximum

burden of 1 VA per input (2 terminals) over the fre-

quency range of 45 to 65 Hz.

SENSING INPUT TYPES

There are 6 sensing input types as defined by the Style

Chart (page 12). The Directional Power Relay’s input

circuitry receives voltage and current signals from

system PTs and CTs. The CT signal is adjusted in level

by a front panel range switch before it is applied to the

kW transducer circuitry. Several input circuit configura-

tions are available, the selection of which is determined

by the specific application. The following paragraphs

provide a brief description of each input sensing type

and their calibration

Type A Sensing: Single-Phase (Figure 7). The type A

sensing configuration monitors line-to-neutral voltage

and a single phase current of a three-phase, four-wire

circuit and calculates the power flowing in the tripping

direction. Relays with this sensing type are calibrated in

single-phase watts.

Type B (60 Hz) or Type V (50 Hz) Sensing: Single-Phase

(Figure 8) with 30° phase shift. This sensing configuration

monitors a line-to-line voltage and a single phase current

of a three-phase, three-wire circuit and calculates the

power flowing in the tripping direction. Since the input

voltage leads the input current by 30° (assuming unity

power factor) a 30° lagging phase shift network is de-

signed into the voltage input circuit. Relays with this

sensing type are calibrated in single-phase watts. Note:

Type B or V configurations are phase rotation sensitive.

Type C Sensing: Three-phase Scott Tee (Figure 9). The

type C sensing configuration monitors three line-to-line

voltages and a single phase current of a three-phase,

three-wire circuit and calculates the power flowing in the

tripping direction. The relay measures actual power even

if the system voltages are not balanced. Relays with this

sensing type are calibrated in three-phase watts.

Figure 7 - Single Phase, Type A Sensing

Figure 9 - Three Phase, Type C Sensing

Figure 8 - Single Phase, Type B or V Sensing

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: