background image

2

BE1-32R, BE1-32R O/U

APPLICATION

PURPOSE

The BE1-32R Directional Overpower Relay and the BE1-

32 O/U, Directional Over/Underpower Relays sense real

power flow (El cos 

Θ

). These relays are solid-state

devices designed for use in single-phase or three-phase

systems to provide equipment protection for overpower

and/or underpower or to be used for supervisory control

of circuits. Both relay configurations may be used to

monitor either forward or reverse power. In the following

application examples, single-phase connections are

shown for simplicity.

APPLICATION EXAMPLES

The BE1-32 relays (R and O/U) are typically used in

applications where excessive power flow in the tripping

direction is indicative of undesirable situations. Typical

examples are discussed below:

Figure 1 - Power Relay Motoring Protection

Figure 2 - Power Relay Start Control

EXAMPLE 1 - ANTI MOTORING

In this example, the power relay is used to protect the

prime mover rather than the generator. When an ac

generator, operating in parallel with a power system,

loses prime mover torque, it remains in synchronism

with the system and continues to run as a synchronous

motor drawing sufficient power from the system to

drive the prime mover. Sustained motoring can cause

severe damage to the prime mover. The Directional

Power Relay, with its wide sensitivity range, can detect

levels of reverse real power flow as low as 0.5 Watts

secondary and provide an alarm or trip the unit off line

(See Figure 1). In this example, single phase sensing is

usually considered sufficient, since motoring is a

balanced condition.

EXAMPLE 2 - COGENERATOR CONTROL

Given that a co-generation system has automatic

engine controls, auto synchronizer, and automatic kW

and kVar controls, the system will virtually operate by

itself. The only functions not readily apparent are the

start/stop signals to the generators. Two system

configurations using a Power Relay may be utilized to

generate contact closures for start and/or stop signals.

The first configuration (Figure 2) shows a power relay

connected to the utility to sense kW. The pickup point

of the relay is set at the maximum desired utility power

level. If the power relay contact closes, the generator

will be started and automatically paralleled with the

utility system. A time delay of 15 seconds or more is

generally included in the “start” circuit  to ignore

transient overload conditions.

Summary of Contents for BE1-32

Page 1: ...rations are available including single phase and three phase 3 and 4 wire systems Sensing ranges available from 0 5 to 6000 watts secondary Instantaneous definite and inverse timing characteristics av...

Page 2: ...and continues to run as a synchronous motor drawing sufficient power from the system to drive the prime mover Sustained motoring can cause severe damage to the prime mover The Directional Power Relay...

Page 3: ...rovide adequate protection for the distribution system the overpower function is used to sense overload conditions on each transformer and the underpower function is used to sense power flowing throug...

Page 4: ...nts If sensing input range 1 4 or 7 is selected the input transformers are capable of 7 A continuous current 10 A for 1 minute and 140 A for 1 second However reactive power is defined by the equation...

Page 5: ...sing type and their calibration Type A Sensing Single Phase Figure 7 The type A sensing configuration monitors line to neutral voltage and a single phase current of a three phase four wire circuit and...

Page 6: ...en 0 9 and 0 5 The range of voltage for proper operation is 40 to 150 percent of the nominal value When the calculated value for power exceeds the over power pickup setting or falls below the underpow...

Page 7: ...nverse time delayed trip is available for the overpower function only The inverse time delay curve is adjust able from 01 to 99 by means of a front panel thumbwheel switch Incrementing the thumbwheel...

Page 8: ...alified to ANSI IEEE C37 90 1 1989 Fast Transient Test IMPULSE TEST Qualified to IEC 255 5 MECHANICAL Operating Temperature 40 C 40 F to 70 C 158 F Storage Temperature 65 C 85 F to 100 C 212 F Weight...

Page 9: ...BE1 32R BE1 32R O U 9 CONNECTIONS Figure 13 Sensing Connections Continued overpage 52 BE1 32 A B C N 5 6 8 9 TYPE A SENSING GENERATOR TRIPPING DIRECTION...

Page 10: ...10 BE1 32R BE1 32R O U CONNECTIONS continued Figure 14 Control Circuits Figure 13 continued Sensing Connections...

Page 11: ...he Style Number Identification Chart and entering its designation letter or number into the appropriate square Two squares are used to indicate time delay characteristics All squares must be completed...

Page 12: ...BER IDENTIFICATION CHART ROUTE 143 BOX 269 HIGHLAND ILLINOIS U S A 62249 PHONE 618 654 2341 FAX 618 654 2351 P A E Les Pins 67319 Wasselonne Cedex FRANCE PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http...

Reviews: