BASI BTC284U Operation Manual Download Page 3

 

Parameter  Symbol 

Description 

Configuration Parameters  

(These parameters are part of Configuration level)

 

Input Type 

inP 

Type of signal that can be connected to the device input

 

Unit 

unit 

Temperature measurement unit  

Point Position 

 

 

 

 

Pnt 

Display decimal point position  

Input Low  

ILo 

Display value at low limit of the linear input range 

Input High  

IHi 

Display value at high limit of the linear input range 

Input Correction  

Icor

Constant to be added to the measured input value 

Address 

Addr 

Device address 

Baud Rate 

bAud 

Serial interface rate 

Gradient 

GrAd 

Maximum input signal change during the sampling period (120 ms) 

Filter Time 

\t 

Relative time constant of the input filter 

Filter Band 

\b 

Zone around the measured value, within which the filter is active 

SP limit Low 

%[L 

Set-point Low limit 

SP limit High 

%[H 

Set-point High limit 

Direction 1 

diR1

 

Control action direction of output 

K1

 

Direction 2 

diR2

 

Control action direction of output 

K2

 

Parameters of the control algorithm

  (These parameters are part of Parametric level)

 

+ Differential 1 

[e1 

Positive Differential of output 

K1

 

- Differential 1 

me1 

Negative Differential of output 

K1

 

Time On 1 

ym1 

ON duration of output 

K1

 

Time Off 1 

y\1 

OFF duration of output 

K1

 

Hold 1 

HLe1 

Holds the output reaction of output 

K1

 

The same 5 parameters, but with index 

2

 -

 

for output 

К

2

 

Parameters of Basic (operating) level

 

Set Point 1 

%[1 

Set-point value of output 

K1

 

Set Point 2 

%[2 

Set-point value of output 

K2

 

 

 
 

Input Filtration 

11 

 

Peak filter 

This filter is intended for eliminating  
pulse spikes (peaks), which can appear 
in the input signal, in the following way: 

 

BTC284U measures the input signal 
value every 120 ms (sample time).

 

 

The measured values are compared 
subsequently. The filter checks 
the difference between the last 
two samples. If it does not exceed 

Gradient

 

value, the device accepts 

the signal as 

normal

.

 

 

If the last measured value differs 
from the previous one by more than 
the 

Gradient

 value, the filter output is held 

until the device determines a presence 
of a 

normal

 signal. It is possible only 

if the input signal has not been changed 
with more than the 

Gradient

 value 

for four subsequent samples.

 

 

If the device has not determined 

normal

 signal for 20 subsequent 

samples, 

noiS

 appears on the display 

(see 'Basic level').

 

Low-pass filter 

This first-order filter acts ONLY within 
a certain band around filter output value.  
This has been designed to cut periodic 
noises outside the communication signal 
spectrum. 

 

Filter operation is defined by two 
parameters: 

Filter Time

 

(defines filter time constant) and 

Filter Band

 

(defines filter active band 

around filter output value). 

 

If the newly measured value differs  
from the filter output by more than 

Filter Band

, the filter resets  

with a new initial output value  
(newly measured value). 
 

 

 

 

 
 

Output Control 

10 

 

 

 

 

 

 
 

 

Control output operation 

 

The control outputs 
operate according  
to the control algorithm 
parameters. 

 

The outputs deactivate 
with the value change 
of one of the following 
configuration 
parameters - 

Point 

Position

,

 

Input Low

,

 

Input 

High

, and

 

Input Correction

 

- and remain inactive

 

till 

Basic level is entered. 

 

The outputs deactivate 
also when an error 
has been detected 
(see

 

'

Error messaging

'). 

ON/OFF control algorithm 

The static characteristic 
of a relay controlled 
by an ON/OFF algorithm 
is shown on the left drawing. 

Output hold 

For eliminating undesirable 
switches of the relay output, 
additional parameter (

Hold

is assigned to hold 
the output reaction 
for certain period of time. 

Output pulse mode 

When a relay is forced  
to ON by the control 
algorithm, it can either  
stay ON or pulse  
depending on 

Time On

 and 

Time Off

 parameter values. 

Setting any of these 
parameters to '0'  
disables the Pulse mode. 

 

Table 1 

Value 

Unit

Notes 

 

Pyh

 or 

Pyt

 

Pt100: -100…850 °C or Pt1000: -100…600 °C 

Ptx1

 or

 

Ptx2

 

PTC 1k or 2k: -50...150 °C 

R)1

resistive linear: 0…1 k

 

yc-b

T/C "B": 200...1800 °C 

yc-J

T/C "J": -20...1000 °C 

yc-"

 

T/C "K": -20...1300 °C 

yc-r

 

T/C "R": 0...1700 °C 

yc-S

T/C "S": 0...1700 °C 

yc-t

T/C "T": -40...400 °C 

u

 

voltage linear: 0…100 mV 

I)20

 or 

I$20

 

current linear: 0…20 mA or 4…20 mA 

w)10

 

voltage linear: 0…10 V 

.C

or 

.F

  

°

C or °F 

x1, x0.1, x0.01, x0.001 

when indicating values with the input-signal measurement unit (

ISU

-1999 ... 9999 

ISU 

These parameters make sense ONLY in case of a linear input signal! 

-1999 ... 9999 

ISU 

OFFSET 

1…254 -  

!2

@4

$8

(6

 

bps 

1200, 2400, 4800 (factory-set), or 9600 bps 

0 … 9999 

ISU 

used for input peak filtration; Value '0' cancels the filtration. 

0 … 9999 

This parameter and the following one define a low-pass input filter. 

0 … 

M

 ISU temperature: whole part of 

M

 

 100; linear: 

M

 = 25% of input range 

within input range 

ISU 

These parameters keep the Set point in safe limits, 

preserving it from random changes. 

cooL

hEAt

  

('

cool

ing' ,  '

heat

ing')

 

These parameters are accessible in the presence of the corresponding relay. 

0 ... 9999 

ISU 

lower than (High input range - 

Set Point 1

)! 

0 ... 9999 

ISU 

lower than (

Set Point 1

- Low input range)! 

0 ... 9999 

sec. 

Value '0' disables Pulse mode. 

0 ... 9999 

sec. 

 

 

These parameters are accessible in the presence of the corresponding relay. 

within input range 

ISU   

 

 
 