User manual - COUNTER
Register Write
Range
Register description
04h
2
Yes
see descr.
State of precounter - this is internal modulo
N
counter, where
N
=
“div”
, overfill of this counter causes incrementation/decrementation of
main counter.
05h
2
Yes
see descr. State of precounter (low word)
06h
2
Yes
see descr. Main counter value - high word
07h
2
Yes
see descr. Main counter value - low word.
08h
Yes
see descr.
State of the relays (binary format)
(1 - on, 0 - off):
00000000 0000dcba
a
- relay R1;
b
- relay R2;
c
- relay R3;
d
- relay R4;
If written, only
a,
b, c,d
bits are important (others are ignored) these
bits allows user to control the relays via RS-485 interface
09h
No
see descr.
The state of relays task in binary format
(1 – relay was being activated (or still is), 0 – relay wasn't being
activated, and will be as soon as result reaches the threshold :
000000000000dcba
a
- relay R1;
b
- relay R2;
c
- relay R3;
d
- relay R4;
This register is very important while relays are being activated on
defined time period. It allows the counter to know if relay was activated
or not.
10h
Yes
0 ÷ 1
“PArUPd”
option (parameters update method):
0
- mode
“immEd”
(update immediately),
1
- mode
“on rES”
(update on reset or power up)
11h
Yes
0 ÷ 2
“Pr inP”
option (programmable input operation mode):
0
- mode
“diSAbL”
, disabled
1
- mode
“dirEct”
, counter direction (function of inputs),
2
- mode
“inhibi”
, holding of the counter.
12h
Yes
0 ÷ 3
“rESEt”
option
(main counter clearing mode):
0
- mode
“ALL”
,
1
- mode
“EL”
, reset with „D” input and RS-485 interface
2
- mode
“mAn”
, reset with
[RESET]
button and RS-485 interface
3
- mode
“nonE”
, reset with RS-485 interface only
13h
Yes
0 ÷ 1
“ArESEt”
option (main counter autoreset):
0
-
“oFF”
, autoreset disabled
1
-
“on Pr1”
, autoreset on relay R1 threhold
2
-
“on 0”
, autoreset below 0 (zero) value
14h
Yes
0 ÷ 9
“FiLtEr”
option
(filtering rate):
0
- for input signal up to 10kHz frequency;
1
- up to 10Hz;
2
- up to 20Hz;
3
- up to 30Hz;
4
- up to 40Hz;
5
- up to 50Hz;
6
- up to 60Hz;
7
- up to 70Hz;
8
- up to 80Hz;
9
- up to 90Hz;
15h
Yes
0 ÷ 3
“Funct”
option (counter operation mode):
0
- normal mode
“A + B”
, addition
1
- normal mode
“A - B ”
, subtraction
2
- quadrature mode
“qUAd 1”
, resolution: incremented by 1 every
single quadrature cycle
3
- quadrature mode
“qUAd 4”
, resolution: incremented by 1 every
one-fourth of single quadrature cycle
38