5.3.3  Connecting the outputs

Depending on load type and current the STG-115 is able 
to directly drive electric loads without any additional driver 
or protection circuit. The Mini-PLC provides 8 digital solid-
state highside outputs and one isolated relay output.

Common features of outputs OUT1 to OUT8 (X6)

•  Rugged solid-state higside switch up to 1.5A
•  Paralleling permissible up to 6A
•  Short circuit protection and current limitation
•  Fast demagnetization of inductive loads
•  Stable behaviour at undervoltage
•  Comprehensive integrated protection circuits
•  Outstanding electromagnetic compatibility (EMC)
•  Electrostatic discharge protection (ESD)

Features of output OUT9 (X5)

•  Relay NO/NC changeover output type 1A/30VDC
•  Electrically isolated
•  Outstanding electromagnetic compatibility (EMC)
•  Electrostatic discharge protection (ESD)

The 9-pole connector X4 named ‚OUT1‘ to ‚OUT8‘ contains 
all digital outputs of the Mini-PLC. While OUT1 to OUT8 are 
overload-protected highside switches, OUT9 (X5) is carried 
out as electrically isolated relay changeover NO/NC switch.
A logical HIGH within miConL will switch the Mini-PLS´s 
supply voltage at OUT1 to OUT8, while the isolated contact 
of OUT9 changes over (NC/NO-NO/NC).
Aviod a current exceeding 1A/30VDC at OUT9 because this 
outputs is not protected against short-circuiting or overload 
current !

The total current sourced by OUT1 to 
OUT8 must not exceed 6A!
Avoid reverse voltage at any output higher 
than the Mini-PLC´s supply voltage!
OUT9 provides NO short circuit protection.
Take care the contact current not exceeds 
1A! Negligence may cause irreversible
damage of the Mini-PLC!

OPERATION AND PROGRAMMING

To operate the STG-115 first establish proper power supply 
connection at both +VDD and GND terminals. 
For programming and PC connection the connection cable 
VK-12 (Art. No. 0091-0012) and a PC with installed Windows 
operating system are mandatory.

Before you connect the Mini-PLC to the PC you have to ins-
tall the USB-/COM-port driver (folder ‚USBdriver‘) from the 
software download package:
www.barth-elektronik.de/download/9045-0008-A.zip

Now install the miConL software suite from the ‚miCon-L‘ 
folder. Follow the setup instructions of miConL. Afterwards 
establish the PC connection using the VK-12 connection 
cable and run miConL.
For choosing the correct COM-Port please click the right 
button (configure serial interface) located on the main menu 
page and confirm the added COM-Port used by the STG-
115.

Now start miConL with creating a new project (Project-> 
New) or open a miCon-L sample application (Project-
>Open).

Summary of Contents for Mini-PLC STG-115

Page 1: ...n 2 4 4 Programming with miCon L 3 4 5 Delivery content 3 5 INSTALLATION 3 5 1 Mounting 3 5 2 Wiring 4 5 3 Overview 4 5 3 1 Connecting the power supply 4 5 3 2 Connecting the inputs 4 5 3 3 Connecting...

Page 2: ...he strict accordance of this manual is important since the installation methods peripheral connections usage and maintenance can not be con trolled by BARTH Elektronik GmbH Therefore BARTH Elektronik...

Page 3: ...lease read the BARTH miCon L manual and the BARTH Application Notes on www barth elektronik de 4 5 Delivery content BARTH Mini PLC STG 115 Spring terminal connectors for supply input output 5 INSTALLA...

Page 4: ...ch 1 of the S1 DIP switch from ON to OFF To change the input IN10 from 4 20mA to 0 10V please set the switch 2 of the S1 DIP switch from ON to OFF Switches 3 and 4 of S1 are not related to any functio...

Page 5: ...NO NC switch A logical HIGH within miConL will switch the Mini PLS s supply voltage at OUT1 to OUT8 while the isolated contact of OUT9 changes over NC NO NO NC Aviod a current exceeding 1A 30VDC at OU...

Page 6: ...ged housing with plugable spring terminal connectors Programming miCon L Software graphical function block style simulation programming and visualisation free license model Interfaces USB reserved for...

Page 7: ...charge ESD on IN1 to IN10 20 kV air discharge 30 kV contact discharge IEC EN 61 000 4 2 level 3 Electrostatic discharge ESD on OUT1 to OUT9 8 kV human body model MIL STD883D Electromagnetic fields Fie...

Page 8: ...e event of any alternation which has not been approved by us being made to any device as designated below this statement shall thereby be made invalid Description Mini PLC Type STG 115 Art No 0850 011...

Reviews: