6.2.1.6
Terminal row “X6“
ATTENTION
MATERIAL DAMAGE DUE TO INCORRECT PRE-FUSING.
Valve or control electronics may be damaged.
Operate the digital outlet valve only with a 1.0 A pre-fuse and the
proportional outlet valve only with a 1.6 A pre-fuse.
The terminal row X6 is used to connect the purge gas valve and the
accompanying valve fuse. Furthermore, the terminal points 6 – 9 are intended for
wires of the LAN connection cable.
Terminal
Connection
Function
1
Pre-fuse
Connection pre-fuse valve
2
Pre-fuse
Connection pre-fuse valve
3
Valve +
+ conductor valve
4
Valve -
GND valve
5
Valve - PE
PE valve
Connection of the original programming cable
6
L1
GN
Send, negative
7
L2
GNWH
Send, positive
8
L3
OG
Receive, negative
9
L4
OGWH
Receive, positive