Scope : 

USER MANUAL 
DE8-BC Ex d Empty Enclosure 

 

      

 

Date: 

02.04.2022 

Ver.: 

QA Code: 

5

 

Checked by: 

E.T. 

Approved by: 

S.Gr. 

Page: 

of 8

 

Document no. : 

21469 

 
 

The passing on and copying of this document and the use or communication of it’s contents are forbidden without express authority. 
Offenders are liable to payment of damages. All rights are  reserved in the event of the registration of a patent . 

  A defective or abnormal use as well as the non compliance with the instructions of the 

present  document  exclude  any  clause  of  guarantee  and  do  not  engage  our 
responsibility 

  The  use  of  the  device  in  case  of  excessive  deposits  of  dusts  superior  at  50mm 

according to EN / IEC 60079-31 is not authorized 

   Liability  for  manufacturer  traceability  is  ensured  only  at  the  first  known  delivery 

destination (serial number specified on the certification label) 

  It is also required to observe the regulations of the country of use 

  The  doors  of  the  DE8-BC  enclosures  are  relatively  heavy,  to  avoid  sagging  of  the 

doors, potentially making the door not align with the flange of the enclosure, the doors 
shall  be  closed  and  secured  during  any  moving  and  shfting  of  the  enclosures.  It  is 
also strongly advisable to close and secure the doors when the daily working shift is 
over 

  The  flame  paths  of  the  doors  and  of  the  flanges  of  the  enclosures  must  be  well 

protected whilst work is performed and ongoing inside the enclosures 

Transport, storage 

  Check it the product has been damaged during transport. If any damage is observed, 

do the statutory reserves to the carrier 

  Do not put damaged products into service 

 

 

Packaging 

Location storage 

Duration storage 

Open 

In a covered location, clean (without contact with 
external substances) and closed with temperature a 
constant humidity (-40°C < T < +70°C). Shielded from 
important temperature variations 

2 years and more with regular inspection (cleanliness 
and mechanical damage) 

Before starting 

  Make sure the unit has been correctly settled and not damaged 

  The device may include any foreign body and no part is damaged 

  The cable gland(s) must be tightened (see description of the gland torque) 

Maintenance 

The  maintenance  and  repairs  works  on  devices  must  be  made  only  by  authorized  and 
trained persons for that purpose. 

 

Before any work the devices must be switched off. In addition: 

  Prevent and avoid any formation of layers of dusts: make a periodic cleaning with a 

wet cloth 

  Do not take apart the command and control units (push buttons, pilot light, etc.) 

 

It is adviseable that the following checks must be made at least once a year:  

  The external equipment and surfaces must not be damaged 

  The cable entry devices and blanking plugs must be securely fastened 

  Prior to closing, check the cleanliness of the flame path (machined part of the cover in 

contact with the machined part of the box). Grease these 2 parts with a thin layer of 
grease  resistant  to  oxidation  (acid  free  white  Vaseline  or  Gleitmo  165). 
Check the gasket for any damage. Replace if damaged. Grease the gasket using acid 
free Vaseline. 

 

Screw  the  cover  on  the  box  using  the  original  bolts  as  listed  in  the  table  below. 

Ensure  that  the  bolts  are  clean  and  are  greased  (grease  like  Gleitmo  165).  Ensure 
that all the bolts are fitted. Torque all bolts to the correct torque as listed in the table 

Summary of Contents for DE8-BC Series

Page 1: ...S Gr Page 1 of 8 Document no 21469 The passing on and copying of this document and the use or communication of it s contents are forbidden without express authority Offenders are liable to payment of...

Page 2: ...d for use in potentially explosive atmospheres and certified according to the requirements of the ATEX Directive and IECEx Parameters relating to safety Maximum current 1000 A Maximum DC voltage 1000...

Page 3: ...ructions The device must be installed used and maintained in accordance with the following standards IEC EN 60079 0 Explosive atmospheres Part 0 Equipment General requirements IEC EN 60079 1 Explosive...

Page 4: ...the carrier Do not put damaged products into service Packaging Location storage Duration storage Open In a covered location clean without contact with external substances and closed with temperature a...

Page 5: ...5 192 274 346 12 14 x M12 35 85 DE8BC 351D 358 478 471 33 250 350 225 192 274 346 12 14 x M12 35 98 DE8BC 43 438 538 321 40 380 400 300 252 334 526 12 14 x M12 35 122 DE8BC 43D 438 538 472 63 380 400...

Page 6: ...Nm 20 C 40 C Qty x L 20 C 40 C DE8BC 32 800 800 12 x M12 35 74 74 DE8BC 32D 800 800 12 x M12 35 74 74 DE8BC 351 800 800 14 x M12 35 74 74 DE8BC 351D 800 800 14 x M12 35 74 74 DE8BC 43 800 800 14 x M1...

Page 7: ...s A C Sides B D Max 2 Sides A C Sides B D Max 2 DE8BC 32 12 12 32 8 8 20 3 3 12 1 1 4 DE8BC 32D 12 12 32 8 8 20 3 3 12 1 1 4 DE8BC 351 12 12 24 8 8 18 3 3 8 1 1 4 DE8BC 351D 12 12 24 8 8 18 3 3 8 1 1...

Page 8: ...the content of the Ex component enclosure equipment may be placed in any arrangement provided that an area of at least 20 IIB or 40 IIB H2 of each cross sectional area remains free The length of flame...