Ex p Control unit
APEX
px
Electrical connections
Rev. 0
01-37A2-7D0001_px_Manual_Exp-Control-Unit_20210923_0_en.docx
Page 45 of 96
Terminal row “X12”
Floating signaling K2 can be classified as pure enable according
to SIL when used.
A floating signal (4x NO) is available on
the Ex p control unit. This signal can
either be used as an enable that is also
safety related.
Or it can be used as a floating signal.
Terminal
Connection
Function
1
K2_1 - NO
Normally open contact
2
K2_2 – NO
Normally open contact
3
K2_3 – NO
Normally open contact
4
K2_4 – NO
Normally open contact
5
K2_1´ - NO
Normally open contact
6
K2_2´ - NO
Normally open contact
7
K2_3´ - NO
Normally open contact
8
K2_4´ - NO
Normally open contact
Terminal row “X7”
ATTENTION
MATERIAL DAMAGE DUE TO INCORRECT PRE-FUSING.
Valve or Ex p control unit may be damaged.
Operate the digital purge gas valve only with a 1.0 A pre-fuse and the
proportional purge gas valve only with a 1.6 A pre-fuse.
The terminal row X7 is used to connect
the purge gas valve and the
accompanying valve fuse. Furthermore,
the terminal points 6 – 9 are intended for
unused wires of the LAN connection
cable.
Terminal
Connection
Function
1
Pre-fuse
Connection pre-fuse valve
2
Pre-fuse
Connection pre-fuse valve
3
Valve +
+ conductor valve
4
Valve -
GND valve
5
Valve - PE
PE valve
6
L1
BU
For unused LAN cable wire
7
L2
BUWH
For unused LAN cable wire
8
L3
BNWH
For unused LAN cable wire
9
L4
BN
For unused LAN cable wire