Operation Instruction (Translation)
MODEX
Regulating and control components
PROFIBUS-Interface 16 x digital out
Typ 07-7331-2301/0000
PROFIBUS-Interface 16 x digital in
Typ 07-7331-2302/0000
EN
GmbH
Max-Eyth-Straße 16
97980 Bad Mergentheim
GERMANY
Phone.:+49 7931 597-0
Fax: +49 7931 597-119
Reservation:
Technical data subject to change without notice.
Changes, errors and misprints may not be used as
a basis for any claim for damages.
4/22
PROFIBUS-Interface 16 x digital out Ex e
Type 07-7331-2301/0000
Electrical Data
Supply voltage electronics
(L+, L-)
DC 24 V (20 – 30) V
Power consumption (L+, L-)
1.5 W
Supply voltage exits
(U+, U-) for emergency stop
switch
DC 24 V (18 - 30) V
Output (L+, L-)
240 W (max.)
Reverse voltage protection
Yes
Max. power loss module
7.3 W
Galvanic isolation
power supply//bus//electronic//
outputs
Bus interface
RS485 with screw clamp
Display
Status
ON, BF, SF
Outputs
16 x LED yellow,
active
Outputs
Output voltage
U+ - 0,18 V
Output current
500 mA at T
U
= + 40 °C
400 mA at T
U
= + 60 °C
Short-circuit protection
Conditionally short-circuit proof
Reverse voltage protection
Yes
Performance monitoring
Collective fault above bus
Power to the outputs can be supplied separately. This power can be
turned off by an emergency stop, for example.
The module has a SYNC function and can freeze on
command of the master the current state of the outputs until
the next SYNC command from the master comes.
PROFIBUS-Interface 16 x digital in Ex e
Type 07-7331-2302/1000
Electrical Data
Supply voltage electronics
(L+, L-)
DC 24 V (20 – 30) V
Power consumption (L+, L-)
1.5 W
Reverse voltage protection
Yes
Max. power loss module
7.3 W
Galvanic isolation
Power supply // bus // inputs
Bus interface
RS485 with screw clamp
Display
Status
ON, BF
Inputs
16 x LED yellow,
active
Inputs
Switching threshold
0 - Signal 0 V to + 5 V
1 - Signal +10 V to +30 V
Power input
typ. 5 mA at 24 V
min. 4 mA at 20 V
Max. power consumption
3.1 W
(max. at 16 active inputs)
Reverse voltage protection
Yes
The module is able FREEZE and can freeze on command
of the master the current state of the inputs until the next
FREEZE command from the master comes.
Product Marking
See page 7 and page 8
5.
Transport and Storage
ATTENTION
Damage due to incorrect storage!
Observe storage and transport temperatures.
Use the original packaging for transport/storage.