TRL Series
Installation Instructions
XXXXXXXX R
EV 1 - 07/23
3
800-533-3948 www.barronltg.com
Operation
The battery in this unit may not be fully charged. After electricity is connected to the unit for at least 24 hours, then normal
operation of this unit should take effect. To check, press the “TEST” button. The EXIT sign should stay illuminated by
battery backup and the LED indicator will be turned off. Release the “TEST” button, LED indicator will be turned on.
In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and
annually for 90 minutes. Refer to your local codes for any additional requirements that may apply.
Testing and Reporting Instructions (-G2 and -G3 models)
1. When AC power is supplied to fixture, the unity will automatically initiate a self-test and self-diagnostic test as follows:
• Verifies battery disconnection, charger board failure at every 5 seconds.
• 1 minute self-testing every month.
• 30 minutes self-testing on every 6 months after installation.
• 90 minutes self-testing on every 12 months after installation.
2. Dual color LED lamp indicator shows the following status:
• Green color: On / Ready
Blinking: Testing
• Red color: (Service Alert)
• Service Alert LED Code (Red color LED lamp indicator)
Note:
After solving the fault of emergency equipment, please press test button for 2 seconds then release to
reset. LED indicator will show green.
2. “-G2” and “-G3” models also have a manual test function, press test button as follows:
Press test button once (within 2 seconds)
Press test button twice (within 2 seconds)
30 seconds discharge test
Press test button 3 times (within 2 seconds)
Press test button 4 times (within 2 seconds)
*Press and hold test button for 8 seconds
3 minutes discharge test
30 minutes discharge test
90 minutes discharge test
Fixture will leave network and reset itself
*Note: only applies to “-G3” models. If you have problem to initiate provisioning or if you know
the unit belongs to other
Guardian
Network
One blink ON/pause (4 seconds)
Two blinks ON/pause (4 seconds)
Battery is not connect
Three blinks ON/pause (4 seconds)
Four blinks ON/pause (4 seconds)
Battery is shorted or battery voltage drops below an acceptable value
Charger board circuit fault
Transfer function failure