background image

Installation, Continued

4. Remove the desired knockouts on the back of the enclosure 

and mount to the J-box using the hardware supplied with the 

J-box.

5. Make electrical connections. All electrical connections should 

be made inside the J-box. Make electrical connection as 

follows: (Fig. 6)

120VAC 

  277VAC

White - Common 

 

White - Common

Black - 120VAC 

 

Orange - 277VAC

Green - Ground 

 

Green - Ground

Note:

 Cap unused leads to prevent shorting. 

6. Flip the cover up and re-secure using (2) 6-32 X 1/4“ 

screws.

7. Open the battery cover by turning the thumb screw 

counterclockwise.

8. Connect the battery, as shown, then secure the 

connector at the bottom left corner of the battery 

compartment (Fig. 7). 

9. Close the door and secure with the thumb screw.

Standard Operation Instructions

1. Energize un-switched AC power to the fixture.

2. Verify the indicator LED or numeric display is illuminated.

3. Press the test button and verify the lamps turn on.

    Note:

 If the lamps do not illuminate, allow the fixture to charge for 30 min.

4. Leave AC connected for the rated charge time prior to performing any full-length test.

5. Refer to the 

Self-Test/Self-Diagnostics (G2)

 section for operation.

 

White 

(Neutral)

Black 

(for 120V)

Orange 

(for 277V)

Green 

(Ground)

Fig. 6

Battery Connection

Knurled Thumb 

Screw

Battery

Fig. 7

 

10070159 

R

EV 8 - 08/22

3

800-533-3948 www.barronltg.com

SCL Series

Installation Instructions

Summary of Contents for EXITRONIX SCL Series

Page 1: ...r electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for ot...

Page 2: ...3c c Once the locknut F is securely in place back up the top nut D to its appropriate position Tighten the bottom nut D securely in place on top of enclosure d Guide the second lock washer C onto the threaded rod G Fig 4 e Guide the 2 mounting plates E onto the threaded rod G f Thread the third lock washer C and third nut D onto threaded rod G g Adjust the mounting brackets to the desired spacing ...

Page 3: ... shown then secure the connector at the bottom left corner of the battery compartment Fig 7 9 Close the door and secure with the thumb screw Standard Operation Instructions 1 Energize un switched AC power to the fixture 2 Verify the indicator LED or numeric display is illuminated 3 Press the test button and verify the lamps turn on Note If the lamps do not illuminate allow the fixture to charge fo...

Page 4: ... will also perform various Self diagnostic tests to determine if there are any faults Visual signaling will alert maintenance personnel to a fault of the emergency unit electronics battery and or battery charger The circuitry continuously monitors the operating condition of the emergency unit and battery charging circuit battery supply voltage Refer to the LED Indicator section below for fault rep...

Page 5: ...atically switch to battery mode every month for a period of 1 minute The unit equipment will automatically switch to battery mode every year for a period of 90 minutes Numeric Indicator The numeric indicator of the emergency unit will display a visual signal indicating the status of the unit Refer to Table 2 for units equipped with a numeric indicator Test Button Features MANUAL TEST Pressing the ...

Reviews: