background image

Fig. 1

Bar Hanger

Recessed Housing

Joists

S900C Series

Installation Instructions

10070218  REV 3 - 09/19

   2

800-533-3948 www.barronltg.com

Recessed Ceiling or Recessed Wall Mount

1. Position the recessed kit between the joists (Fig. 1).

    NOTE:

 If using a single face EXIT sign, make sure to position the 

    recessed kit such that when the EXIT panel assembly is installed, it 

    will be in the correct orientation. This is determined by matching up 

    the location of the EXIT panel connector within the trim plate 

    assembly (see Fig. 2) and the location of the EXIT panel 

    connector on the EXIT panel (see Fig. 3 & 4). 

2. Align one end of the bar hangers with the bottom of the joists, 

    then secure temporarily by hammering in the “nail-in” tabs. 

    Loosen the bar hanger set screws on both sides of the recessed 

    housing. Align the other end of the bar hangers to the opposing joist 

    and hammer in the “nail-in” tabs.
3. Once the bar hangers are aligned properly, permanently secure 

    the bar hangers by hammering in the nails.
4. With the bar hanger set screws still loose, adjust the horizontal 

    placement of the recessed housing between the joists by sliding along 

    the bar hangers. Secure by tightening the bar hanger set screws.
5. Adjust the vertical placement of the recessed housing by loosening the 

    vertical slot set screws, then raising or lowering the recessed housing.  

    The recessed housing should be positioned such that the trim plate will 

    be flush with the ceiling or wall when installed. Secure by tightening the 

    vertical slot set screws.

6. Separate the trim plate assembly from the housing by loosening the (2) 

    screws on either end of the trim plate. The spring hangers will keep the 

    trim plate assembly from falling (Fig. 2).

7. Loosen the end of the trim plate assembly closest to the wire 

    compartment by pinching the spring hanger and guiding its ends out 

    through the opening in the housing. Carefully lower the loosened end 

    of the trim plate assembly until it is supported by the safety cable.
8. Connect the battery/batteries to the PCB.
9. Remove the wire compartment cover and set aside.

10. Route wires into the wire compartment.
11. Make electrical connections; see 

Electrical Connections

 section.

12. Push excess wire into the wire compartment, then replace the wire 

      compartment cover.
13. Reposition the spring hanger into the recessed housing, then slide the 

      trim plate assembly back into the recessed housing and secure with the 

      (2) screws.

14. Connect the EXIT panel assembly to the PCB, then secure by sliding 

      into the EXIT panel slot in the trim plate (Fig. 3 & 4).

Fig. 2

Trim Plate Assembly

Safety 

Cable

Spring Hanger

Wire 

Compartment

Cover

EXIT Panel

Connector

Fig. 4

Lamp Heads

EXIT Panel

Connector

Fig. 3

EXIT Panel

Connector

Trimplate 

Screws

Trimplate

Vertical Slot Set Screws

Bar Hanger Set Screws

Vertical Slot Set Screws

Bar Hanger Set Screws

Nail-in 

Tab

Nail

EXIT Panel

EXIT Panel

Wire

Compartment

Summary of Contents for Exitronix S900C Series

Page 1: ...o not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than intended use ...

Page 2: ... The recessed housing should be positioned such that the trim plate will be flush with the ceiling or wall when installed Secure by tightening the vertical slot set screws 6 Separate the trim plate assembly from the housing by loosening the 2 screws on either end of the trim plate The spring hangers will keep the trim plate assembly from falling Fig 2 7 Loosen the end of the trim plate assembly cl...

Page 3: ...canopy 8 Slide the trim plate assembly fully into the housing and remove the excess slack from the wires inside the housing by pulling them farther out through the canopy Replace the end plate and secure with the 4 screws 9 Make electrical connections see Electrical Connections section 10 Secure the unit to the adjustable crossbar using the 2 M4 x 40mm screws supplied Ensure the canopy is securely...

Page 4: ...C Orange 277VAC Note Cap unused wires to prevent shorting S900C Series Installation Instructions 10070218 REV 3 09 19 4 800 533 3948 www barronltg com LAMP 1 LAMP 2 LAMP 3 BATT 1 BATT 2 JK2 JK1 LED Strip LED Switch INPUT 1st Battery 2nd Battery Orange 277VAC Black 120VAC White Common Built in Built in Remote Lamps ...

Page 5: ...e unit is undergoing a test A blinking red LED indicates whenever the Self diagnostic system has detected a fault condition Refer to the chart below when the LED is blinking red Test Button Features MANUAL TEST Pressing the test button will switch the unit into battery mode for a set amount of time The desired length of the test is determined by the number of times the test button is pressed Press...

Reviews: