Self-Test/Self-Diagnostics (G2)
Operation
The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the EXIT sign. At predetermined
intervals, the EXIT sign will automatically switch into battery mode. Refer to the
Self-Test Features
section
of this page
for timing details. The EXIT sign will also perform various Self-diagnostic tests of the EXIT sign. The circuitry continuously
monitors the operating condition of the EXIT sign and battery charging circuit. Visual signaling will alert maintenance
personnel to a fault of the EXIT sign electronics, emergency lamps, battery, and/or battery charger. Refer to the
LED
Indicator
section below for fault reporting details.
Self-Test Features
• The EXIT sign will automatically switch to battery mode every month for a period of 1 minute.
• The EXIT sign will automatically switch to battery mode every 6 months for a period of 30 minutes.
• The EXIT sign will automatically switch to battery mode every 12 months for a period of 90 minutes.
LED Indicator
The unit is equipped with a bi-color LED, which displays either green or red.
• A steady green LED indicates that normal AC power is being supplied to the EXIT sign.
• A flashing green LED indicates that the EXIT sign is undergoing a test.
• A blinking red LED indicates whenever the Self-diagnostic system has detected a fault condition. Refer to the chart
below when the LED is blinking red:
Test Button Features
MANUAL TEST – Pressing the test button will switch the EXIT sign into battery mode for a set amount of time. The
desired length of the test is determined by the number of times the test button is pressed.
• Pressing the test button once will switch the EXIT sign into battery mode for 30 seconds.
• Pressing the test button twice within 2 seconds will switch the EXIT sign into battery mode for 3 minutes.
• Pressing the test button 3 times within 2 seconds will switch the EXIT sign into battery mode for 30 minutes.
• Pressing the test button 4 times within 2 seconds will switch the EXIT sign into battery mode for 90 minutes.
RESET – Pressing and holding the test button for 2 seconds will reset the LED to a steady green. If multiple faults are
present, it may be necessary to repeat this procedure for each remaining fault indicated by the blinking red LED.
Use in accordance with local building codes.
Number of Blinks
1
2
3
4
5
6
7
Unit Fault
Battery Disconnected
Battery
Charge
Transfer (AC to DC)
Emergency Lamp
Remote Lamp
EXIT Panel
Corrective Action
Check Battery Connection
Replace Battery
Charger Board Circuit Fault
Transfer Function Failure
Check Lamp Connections Then Consult Factory
Check Remote Lamp Connections Then Consult Factory
Check EXIT Panel Connections Then Consult Factory