BARRON Exitronix NY900C Series Installation Instructions Download Page 3

Surface Ceiling or Surface Wall Mount

1. Secure the adjustable crossbar to the J-box using the (2) 8-32 x 1” 

    screws (supplied). Use the slotted portion of the adjustable crossbar to 

    mount to the J-box and position such that the portion with the threaded 

    holes is facing out from the J-box. (Fig. 5)

2. Punch out the desired knockouts located in the top or side of the 

    enclosure for ceiling or wall mounting, respectively. Insert the plastic 

    grommet (supplied) into the center hole.
3. Attach the canopy to the enclosure using the (2) M4 x 8mm screws 

    (supplied).
4. Insert the (2) plastic rivets (supplied) into the (2) unused M4 holes in the 

    enclosure.

5. Remove one of the enclosure end caps by removing the (4) screws and 

    set all aside. Slide the trimplate assembly out of the housing.

6. Connect the battery/batteries to the PCB.
7. Slide the trimplate assembly partially into the enclosure so that the wires 

    can be routed through the canopy, then route the wires through the 

    canopy.

8. Slide the trimplate assembly fully into the enclosure and remove the 

    excess slack from the wires inside the enclosure by pulling them farther 

    out through the canopy. Replace the end cap and secure with the 

    (4) screws from Step 5.
9. Make electrical connections; see 

Electrical Connections

 section.

10. Secure the fixture to the adjustable crossbar using the (2) M4 x 40mm 

      screws (supplied). Ensure the canopy is securely fastened against the ceiling or wall and will not rotate.

11. Connect the EXIT panel assembly to the PCB with the EXIT panel connector, then secure by sliding into the EXIT panel 

      slot in the trimplate until it locks into place. Verify that the EXIT panel is properly secured by lightly pulling the EXIT 

      panel assembly away from the trimplate. (Fig. 6)

    NOTE:

 If using a single face EXIT sign, it may be necessary to change the direction the EXIT panel is facing. This is 

    determined when the EXIT panel assembly is secured within the trimplate. To change the direction of the EXIT panel, 

    pull one end of the EXIT panel out of the EXIT panel light bar, followed by the other end. Rotate the EXIT panel 180° 

    then reinstall the EXIT panel within the EXIT panel light bar. 

12. Remove the protective film from the EXIT panel to complete the installation.

 

 

Remote Lamps

If the fixture is installed with the remote capable option, the fixture can support 3.6VDC 3W max. remote capabilities. 

Compatible with two RL1 remote lamps (non-G2 models) or one RL1 remote lamp (G2 models).

To connect the remote head(s) to the fixture: 

1. Remove the jumper, if present, and discard.

2. Connect the remote wires to the remote connector. Yellow is positive (+) and purple is negative (-). 

3. Plug the remote connector into the female connector on the PCB labeled Lamp 3. 

Fig. 6

Lamp Head

EXIT Panel

Connector

EXIT Panel

EXIT Panel

Light Bar

Protective 

Film

Fig. 5

Above: Top Mount

Right: Wall Mount

J-box

Adjustable 

Crossbar

Canopy

Enclosure

End Cap

J-box

J-box

NY900C Series

Installation Instructions

 

10070221 

R

EV 3 - 01/21

800-533-3948 www.barronltg.com

3

Summary of Contents for Exitronix NY900C Series

Page 1: ...ot use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than intended use All...

Page 2: ...ct the battery batteries to the PCB 9 Remove the wire compartment cover and set aside 10 Route wires into the wire compartment 11 Make electrical connections see Electrical Connections section 12 Push excess wire into the wire compartment then replace the wire compartment cover 13 Reposition the spring hanger into the recessed housing then slide the trimplate assembly back into the recessed housin...

Page 3: ...nst the ceiling or wall and will not rotate 11 Connect the EXIT panel assembly to the PCB with the EXIT panel connector then secure by sliding into the EXIT panel slot in the trimplate until it locks into place Verify that the EXIT panel is properly secured by lightly pulling the EXIT panel assembly away from the trimplate Fig 6 NOTE If using a single face EXIT sign it may be necessary to change t...

Page 4: ...Orange 277VAC Note Cap unused wires to prevent shorting INPUT LAMP 1 LAMP 2 LAMP 3 BATT 2 JK2 JK1 LED Strip LED Switch Battery 1 Orange 277VAC Black 120VAC White Common Built in BATT 1 Remote Lamps Built in Battery 2 Fig 7 NY900C Series Installation Instructions 10070221 REV 3 01 21 800 533 3948 www barronltg com 4 ...

Page 5: ...diagnostic system has detected a fault condition Refer to the chart below when the LED is blinking red Test Button Features MANUAL TEST Pressing the test button will switch the EXIT sign into battery mode for a set amount of time The desired length of the test is determined by the number of times the test button is pressed Pressing the test button once will switch the EXIT sign into battery mode f...