Self-Test/Self-Diagnostics (G2)

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the emergency unit. At 

predetermined intervals, the emergency unit will automatically switch into battery mode. Refer to the 

Self-Test Feature

 

section below for timing details. The emergency unit will also perform various Self-diagnostic tests to determine if there 

are any faults.  Visual signaling will alert maintenance personnel to a fault of the emergency unit electronics, battery, 

and/or battery charger.  The circuitry continuously monitors the operating condition of the emergency unit and battery 

charging circuit/battery supply voltage. Refer to the 

LED Indicator

 section below for fault reporting details.

Self-Test Feature

• The emergency unit will automatically switch to battery mode every month for a period of 1 minute.

• The emergency unit will automatically switch to battery mode every 12 months for a period of 90 minutes.

LED Indicator

Once the unit is properly installed according to the installation instruction sheet and AC power is supplied, the unit will turn 

on and the Self-diagnostic test function will initiate.  After this, the bi-color LED will indicate the status of the unit.

• A steady green LED indicates that normal AC power is being supplied to the emergency unit and the battery is 

charged.

• A blinking green LED indicates that the unit is in battery mode.  Refer to the 

Test Button Feature 

section below for 

manual test details.

• A red LED indicates whenever the Self-diagnostic system has detected a fault condition.  Refer to the chart below to 

determine the fault condition:

Test Button Feature

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired 

length of the test is determined by the number of times the test button is pressed.

• Pressing the test button once will switch the unit into battery mode for a period of 30 seconds.

• Pressing the test button twice within 2 seconds will switch the unit into battery mode for a period of 3 minutes.

• Pressing the test button 3 times within 2 seconds will switch the unit into battery mode for a period of 30 minutes.

• Pressing the test button 4 times within 2 seconds will switch the unit into battery mode for a period of 90 minutes.

RESET – If the fixture is in self-test mode, pressing the test button once will cancel the test. After solving the fault of 

emergency equipment, pressing and holding the test button for 2 seconds then releasing will reset the LED indicator to 

steady green.

Use in accordance with local building codes.

Red LED Indication

Blinking 1 Time

Blinking 2 Times

Blinking 3 Times

Blinking 4 Times

Blinking 5 Times
Blinking 6 Times

Unit Fault

Battery is Disconnected

Battery Failure

Charger Board Circuit Fault

Transfer Function Failure

Emergency Lamp Fault

Remote Lamp (If Equipped)

Corrective Action

Check Battery Connection

Check Battery Then Consult Factory
Check Battery Then Consult Factory
Check Battery Then Consult Factory

Check Lamp Connections Then Consult Factory

Check Remote Lamp Connections Then Consult Factory

10070204 

R

EV 5 - 05/22

4

800-533-3948 www.barronltg.com

LED-51/52 Series

Installation Instructions

Summary of Contents for EXITRONIX LED-51 Series

Page 1: ...er cords touch hot surfaces Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than inte...

Page 2: ...lots to remove the front cover from the backplate Fig 1 2 Remove appropriate knockouts from backplate and mount to wall 3 Remove the top knockout on the top flange of the fixture for the flexible conduit access hole Fig 4 4 Secure conduit or surface raceway to the top hole and feed wires 5 Make electrical connections see Electrical Connections section 6 Connect remote lamp wires if the fixture is ...

Page 3: ... on and the LED indicator light will turn off Release the test switch the LED indicator will turn on and the LED heads will turn off Troubleshooting Guide If the LED heads or the LED indicator do not illuminate check the following 1 Check AC supply verify that the unit has 24 hours AC supply 2 Check the battery connections 3 Discharge the battery and charge the battery for 24 hours or 48 hours for...

Page 4: ...es whenever the Self diagnostic system has detected a fault condition Refer to the chart below to determine the fault condition Test Button Feature MANUAL TEST Pressing the test button will switch the unit into battery mode for a set amount of time The desired length of the test is determined by the number of times the test button is pressed Pressing the test button once will switch the unit into ...

Reviews: