If pump is installed with a discharge hose rather than a
moveable fi tting assembly, make sure the discharge pipe
has a 1/8” dia. hole approx. 5” from end nearest volute and
oriented towards the pump body.
ELECTRICAL CONNECTIONS:
Pump Cords -
The quick connect cord assembly mounted
to the pump must
NOT
be modifi ed in any way except for
shortening to a specifi c application. Any supply cables
connections between the pump and the control panel must
be made in accordance with the National Electric Code
or the Canadian Electric Code and all applicable state,
province and local electric codes. It is recommended that a
junction box, be mounted outside the sump or be of at least
Nema 4 (EEMAC-4) construction if located within the wet
well.
DO NOT USE THE POWER OR CONTROL CABLES
TO LIFT PUMP!
Overload Protection -
The type of in-winding overload
protector used is referred to as an inherent overheating
protector and operates on the combined effect of temperature
and current. This means that the overload protector will trip
out and shut the pump off if the windings become too hot,
or the load current passing through them becomes too high.
It will then automatically reset and start the pump up after
the motor cools to a safe temperature. In the event of an
overload, the source of this condition should be determined
and rectifi ed immediately.
DO NOT LET THE PUMP CYCLE
OR RUN IF AN OVERLOAD CONDITION OCCURS !
Wire Size -
If additional cord is required consult a qualifi ed
electrician for proper wire size.
CORD CONNECTIONS:
Power/Control Cord-
Insert female end of cord plug into
housing bore aligning alignment mark with hole in terminal
block see Figure 3. Tighten bolts on compression fl ange
until fl ush with motor housing.
FIGURE 3
FIGURE 2